| 2016-06-15 17:30:10 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - PLEASE COMPLY WITH BUILDING COMMENTS FOR FINAL | | | APPROVAL | | | | | | - NEC 680.21(C) GFCI PROTECTION REQUIRED FOR OUTLETS | | | SUPPLYING POOL PUMP MOTORS CONNECTED TO SINGLE PHASE | | | 120 V THROUGH 240 V BRANCH CIRCUITS, RATED 15 OR 20 | | | AMPS WHETHER BY RECEPTACLE OR BY DIRECT CONNECTION, | | | SHALL BE PROVIDED WITH GROUND FAULT CIRCUIT INTERRUPTER | | | PROTECTION FOR PERSONNEL. |
|