| Plan Review Notes For Permit 16060084 |
| Permit Number |
16060084 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-30 14:40:40 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - NFPA 37 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND | | | THEIR WEATHERPROOF HOUSINGS IF PROVIDED, THAT ARE | | | INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 1.5 M (5 | | | FT) FROM OPENINGS IN WALLS AND AT LEAST 1.5 M (5 FT) | | | FROM STRUCTURES HAVING COMBUSTIBLE WALLS. | | | A MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER | | | OF THE FOLLOWING CONDITIONS EXIST: | | | | | | (1) THE ADJACENT WALL OF THE STRUCTURE HAS A FIRE | | | RESISTANCE RATING OF AT LEAST 1 HOUR. | | | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED | | | THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE | | | COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. | | | | | | PLEASE CLARIFY ? SITE PLANS SHOW NO WINDOWS WITHIN 10' | | | HOW ABOUT ROOF OVERHANG VENT OPENINGS ? |
|