2016-09-07 17:16:17CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
  
 (1) PROVIDE CORRECT TOTAL CFM VALUES FOR A/C SYSTEM #1.
 AS PER PLANS EQUIPMENT SCHEDULE AND FBC ENERGY/HEAT
 LOAD CALCULATIONS SYSTEM #1 AHU PROVIDES A TOTAL OF
 2000 CFM. AS PER THE PLANS NOTED SUPPLY OUTLET CFM, AHU
 #1 TOTAL CFM IS 2450. THIS DOES NOT MATCH THE SUBMITTED
 DOCUMENTS.
  
 (2) PROVIDE CORRECT TOTAL CFM VALUES FOR A/C SYSTEM #2.
 AS PER PLANS EQUIPMENT SCHEDULE AND FBC ENERGY/HEAT
 LOAD CALCULATIONS SYSTEM #1 AHU PROVIDES A TOTAL OF
 1400 CFM. AS PER THE PLANS NOTED SUPPLY OUTLET CFM, AHU
 #1 TOTAL CFM IS1100. THIS DOES NOT MATCH THE SUBMITTED
 DOCUMENTS.
  
 PROVIDE A BALANCED CFM AMOUNT FOR BOTH A/C SYSTEMS #1
 AND #2.
  