| 2016-09-07 17:16:17 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | | | | (1) PROVIDE CORRECT TOTAL CFM VALUES FOR A/C SYSTEM #1. | | | AS PER PLANS EQUIPMENT SCHEDULE AND FBC ENERGY/HEAT | | | LOAD CALCULATIONS SYSTEM #1 AHU PROVIDES A TOTAL OF | | | 2000 CFM. AS PER THE PLANS NOTED SUPPLY OUTLET CFM, AHU | | | #1 TOTAL CFM IS 2450. THIS DOES NOT MATCH THE SUBMITTED | | | DOCUMENTS. | | | | | | (2) PROVIDE CORRECT TOTAL CFM VALUES FOR A/C SYSTEM #2. | | | AS PER PLANS EQUIPMENT SCHEDULE AND FBC ENERGY/HEAT | | | LOAD CALCULATIONS SYSTEM #1 AHU PROVIDES A TOTAL OF | | | 1400 CFM. AS PER THE PLANS NOTED SUPPLY OUTLET CFM, AHU | | | #1 TOTAL CFM IS1100. THIS DOES NOT MATCH THE SUBMITTED | | | DOCUMENTS. | | | | | | PROVIDE A BALANCED CFM AMOUNT FOR BOTH A/C SYSTEMS #1 | | | AND #2. | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|