| Plan Review Notes For Permit 16060012 |
| Permit Number |
16060012 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-03 09:29:55 | 1) PER SEC.1003.2 OF 2014 FBC-PLUMBING, THE SIZE, TYPE | | | AND LOCATION OF EACH INTERCEPTOR SHALL BE APPROVED BY | | | THE PLUMBING OFFICIAL. SUBMIT FACTORY SIZING | | | CALCULATIONS PERFORMED BY SCHIER TO ENSURE THE CORRECT | | | SIZING OF THE INTERCEPTOR. CONTACT LEE SCHNEEWEISS, | | | FACTORY REPRESENTATIVE, AT 1-800-538-4792. | | | 2) FYI - ON SHT.P5.1 IN THE GREASE INTERCEPTOR | | | CALCULATIONS - THE NUMBER OF HOURS NEEDS TO SHOW THAT | | | IT IS DIVIDED BY 12 TO CORRELATE WITH THE GREASE | | | CAPACITY NEEDED. | | | 3) A SAMPLING PORT IS REQUIRED IN THE DISCHARGE LINE | | | FROM THE GREASE INTERCEPTOR. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|