Plan Review Notes
Plan Review Notes For Permit 16060011
Permit Number 16060011
Review Stop B
Sequence Number 4
Notes
Date Text
2017-07-11 09:41:07RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT ITEMS REQUIRED BELOW MAY BE SUBMITTED LATER
 AFTER THE PERMIT IS ISSUED, BUT BEFORE INSPECTIONS TO
 AVOID DELAYS/CONFLICTS. REVISION FEES WILL APPLY.
 CONTRACTOR OR OWNER TO RESPOND IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME (IT MAY BE DONE BY
 RESPONDING TO THIS E-MAIL).
  
 1- ENERGY CALCULATIONS SUBMITTED:
 NOTE: NEW ENERGY CALCULATIONS WERE SUBMITTED. NEW
 ENERGY CALCULATIONS WERE DONE BY ANOTHER PREPARER AND
 THE FORM USED IS THE PRESCRIPTIVE FORM R402-2014. THE
 FOLLOWING COMMENTS APPLY TO THE NEW FORM SUBMITTED:
 A) IF USING THE PRESCRIPTIVE METHOD TO SHOW COMPLIANCE
 WITH THE ENERGY CODE, THEN ALL THE PRESCRIPTIVE
 REQUIREMENTS OF TABLE R402A MUST BE MET. THE PROPOSED
 ADDITION IS CONCRETE BLOCK. TABLE R402A REQUIRES A
 MINIMUM OF R-4 INSULATION ON THE INTERIOR OF THE WALL
 AND A MINIMUM OF R3 INSULATION ON THE EXTERIOR OF THE
 WALL. PLANS SUBMITTED DON'T COMPLY WITH THIS
 REQUIREMENTS. PERSON PREPARING THE ENERGY CALCULATIONS
 TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THIS REQUIREMENTS. ENGINEER OF RECORD TO
 REVISE PLANS AS WELL. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) INFORMATION SHOWN ON ITEM #9A1 IS INCORRECT. WALL
 TYPE IS MASONRY NOT WOOD FRAME. REVISE AS REQUIRED TO
 MATCH PLANS AND TABLE R402A. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 C) PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 A/C MANUFACTURER'S INFORMATION SHOWING THE SEER 20
 EQUIPMENT EFFICIENCY SPECIFIED ON ITEM #12 B. SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 D) ITEM #14 SPECIFIED THAT HVAC CALCULATIONS ARE NOT
 ATTACHED. EQUIPMENT SIZING CALCULATIONS ARE REQUIRED.
 PROVIDE THE CALCULATIONS AND REVISE ITEM #14 AS
 REQUIRED. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED.
  
  
 ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS.
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS.
 SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]