| 2017-05-26 08:20:18 | RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS THAT ITEMS REQUIRED BELOW MAY BE SUBMITTED LATER |
| | AFTER THE PERMIT IS ISSUED, BUT BEFORE INSPECTIONS TO |
| | AVOID DELAYS/CONFLICTS. REVISION FEES WILL APPLY. |
| | CONTRACTOR OR OWNER TO RESPOND IN WRITING IF PROVISO |
| | OPTION IS PREFERRED AT THIS TIME (IT MAY BE DONE BY |
| | RESPONDING TO THIS E-MAIL). PERMIT WILL BE PROCESSED |
| | ONCE WE RECEIVE THE PLANS WITH THE COUNTY IMPACT FEES |
| | STAMP AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 1- THE NORTH ARROW ORIENTATION SHOWN IN ALL PLANS IS |
| | INCORRECT. SEE SURVEY AND REVISE AS REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. THREE TIMES. RESPONSE LETTER |
| | STATES " COMMENT WAS ADDRESSED IN PREVIOUS REVISION. |
| | WHEN HOUSE IS ROTATED ABOUT 22 DEGREES CLOCKWISE THE |
| | NORTH ARROW ALSO ROTATES AN EQUIDISTANT AMOUNT. ". THIS |
| | IS THE TRUE, BUT THE PROBLEM IS THAT THE NORTH ARROW |
| | ORIENTATION WAS WRONG SINCE THE BEGINNING. SEE SURVEY |
| | AND REVISE AS REQUIRED. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED; |
| | A) REVISE WINDOWS INFORMATION ON PAGE 3 OF 4. WINDOWS |
| | AND DOORS WITH GLAZING ARE NOT VINYL FRAME. SEE PRODUCT |
| | APPROVALS AND REVISE AS REQUIRED. R101.5.1.1.1 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. RESPONSE LETTER STATES "THIS |
| | COMMENT WAS ADDRESSED IN THE PREVIOUS REVISION. |
| | MECHANICAL PLAN REVIEWER APPROVED IT AND PASSED ITS |
| | REVISION." MECHANICAL PLAN REVIEWER APPROVED THE |
| | MECHANICAL PLAN AND EQUIPMENT LOAD CALCULATIONS. THE |
| | ENERGY CALCULATIONS WERE APPROVED BY ME WITH THE |
| | CONDITION THAT WINDOW MATERIAL IS REVISED. |
| | |
| | NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING |
| | THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY |
| | CALCULATIONS WILL BE REQUIRED WHEN THE ENERGY |
| | CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT FACTOR |
| | FOR GLAZING. |
| | |
| | |
| | ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS. |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS. |
| | SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW |
| | PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTION, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |