| 2016-11-29 18:45:52 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | NOTES: |
| | (A) COORDINATE WITH ZONING COMMENTS. |
| | |
| | (B) BUILDING REVIEW MAY BE APPROVED WITH PROVISO. |
| | PROVISO MEANS THAT ITEMS REQUIRED BELOW MAY BE |
| | SUBMITTED LATER AFTER THE PERMIT IS ISSUED, BUT BEFORE |
| | INSPECTIONS TO AVOID DELAYS/CONFLICTS. REVISION FEES |
| | WILL APPLY. CONTRACTOR OR OWNER TO RESPOND IN WRITING |
| | IF PROVISO OPTION IS PREFERRED AT THIS TIME. |
| | |
| | |
| | 1- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOMS, |
| | INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC. R315 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: |
| | ELECTRICAL PLANS ONLY SHOW CARBON MONOXIDE ALARM FOR |
| | THE ADJACENT BEDROOM. THERE ARE MORE BEDROOMS IN THIS |
| | HOUSE. NEED TO PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| | FEET OF EACH BEDROOM. |
| | |
| | 2- THE NORTH ARROW ORIENTATION SHOWN IN ALL PLANS IS |
| | INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED; |
| | A) REVISE WINDOWS INFORMATION ON PAGE 3 OF 4. WINDOWS |
| | AND DOORS WITH GLAZING ARE NOT VINYL FRAME. SEE PRODUCT |
| | APPROVALS SUBMITTED AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING |
| | THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY |
| | CALCULATIONS WILL BE REQUIRED WHEN THE ENERGY |
| | CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT FACTOR |
| | FOR GLAZING. |
| | |
| | |
| | ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS. |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS. |
| | SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW |
| | PROCESS. |
| | |