Plan Review Notes
Plan Review Notes For Permit 16060011
Permit Number 16060011
Review Stop P
Sequence Number 1
Notes
Date Text
2016-06-16 15:18:15PLUMBING COMMENTS:
  
 1. VALUE OF JOB APPEARS LOW. PER WPB AMEND. TO FBC SEC.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2.SANITARY PIPING ON FLAT PLAN DOES NOT MATCH RISER
 DIAGRAM PLEAS CLARIFY. PER WPB AMEND. TO FBC SEC.
 107.2.1
  
 3. HORIZONTAL DRY VENT ON SHOWER NOT ALLOWED. PER FBC
 PL SEC. P3104.3- P3104.4
  
 4. SHT. E-1 SHOWS HORIZONTAL DRY VENT NOT ALLOWED. PER
 FBC PL SEC. P3104.3- P3104.
  