| 2016-06-30 11:11:57 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. PLEASE VERIFY THE INDICATED SCALE TO MATCH THE |
| | ACTUAL INTENDED. THIS MAY ALTER THE OUTLET PLACEMENT |
| | REQUIREMENTS AS PER NEC 210.52. |
| | 2. CORRECT ELECTRICAL NOTE 2 TO SHOW THE CORRECT CODES. |
| | ALL WORK SHALL BE AS PER THE 5TH EDITION OF THE FBC |
| | 2014 RATHER THAN THE SOUTH FLORIDA BLDG. CODE AS WELL |
| | AS THE 2011 EDITION OF THE NEC. |
| | 3. CORRECT ELECTRICAL NOTE 7 AS ARTICLE 370 OF THE 2011 |
| | NEC ADDRESSES CABLE BUS. THE ARTICLE ADDRESSING |
| | JUNCTION BOXES IS 314. |
| | 4. PER NEC 406.12 ALL NEWLY INSTALLED RECEPTACLES IN |
| | DWELLING UNITS SHALL BE LISTED AS ?TAMPER-RESISTANT?. |
| | ADD THIS NOTE TO THE ELECTRICAL NOTES. |
| | 5. PER NEC 250.94 THE INTER-SYSTEM BONDING TERMINAL |
| | SHALL BE AT THE SERVICE OR METER. CORRECT YOUR RISER |
| | DIAGRAM AS NOTED. |
| | 6. PER NEC 210.70(A)(3) THE ATTIC LIGHT SWITCH SHALL BE |
| | ON A WALL ADJACENT TO THE POINT OF ENTRY. MAY I SUGGEST |
| | A SWITCH WITH A PILOT LIGHT TO INDICATE STATUS LOCATED |
| | IN A VISIBLE LOCATION. |
| | 7. PER NEC 210.52(A) THE WALL BETWEEN THE CLOSET AND |
| | BATHROOM DOOR IS MISSING AN OUTLET. |
| | 8. PER NEC 210.52(A) THE ROOM JUST OUTSIDE THE BEDROOM |
| | DOOR IS MISSING OUTLETS. MAY I SUGGEST A 3 WAY SWITCH |
| | FOR THE LIGHT AS WELL. |
| | 9. PER NEC 680.73 THE POWER SOURCE OUTLET SHALL BE |
| | READILY ACCESSIBLE AND FACING THE OPENING IF |
| | APPLICABLE. THIS DEVICE SHALL BE NO MORE THAN 1 FOOT |
| | AWAY FROM THE OPENING. |
| | 10. PER NEC 680.74 ALL METAL PARTS ASSOCIATED WITH OR |
| | IN CONTACT WITH THE CIRCULATING WATER SHALL BE BONDED |
| | WITH A #8 COPPER CONDUCTOR WHICH SHALL BE CONNECTED TO |
| | THE PUMP MOTOR AND FOR EQUIPOTENTIAL BONDING. |
| | 11. PER NEC 440 PART II A DISCONNECT FOR THE MINI-SPLIT |
| | CONDENSING UNIT IS REQUIRED. |
| | 12. PER FBC 314.3 YOU SHALL HAVE A SMOKE DETECTOR |
| | ?INSIDE? THE SLEEPING AREA AND ALSO IN THE IMMEDIATE |
| | AREA OUTSIDE. CORRECT THE DEVICE PLACEMENT AS INDICATED |
| | ON THE PLANS. |
| | 13. PER FBC 314.3.1 YOU SHALL INSTALL SMOKE DETECTORS |
| | THROUGHOUT THE RESIDENCE AS REQUIRED FOR NEW |
| | CONSTRUCTION. IF ALREADY DONE SO, DISREGARD THIS |
| | COMMENT. |
| | 14. PER FBC 315 IF THE RESIDENCE HAS AN ATTACHED GARAGE |
| | OR ANY FOSSIL FUEL BURNING APPLIANCE YOU SHALL INSTALL |
| | CARBON MONOXIDE DETECTORS AS INDICATED BY THIS SECTION. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |