2016-06-30 11:11:571ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. PLEASE VERIFY THE INDICATED SCALE TO MATCH THE
 ACTUAL INTENDED. THIS MAY ALTER THE OUTLET PLACEMENT
 REQUIREMENTS AS PER NEC 210.52.
 2. CORRECT ELECTRICAL NOTE 2 TO SHOW THE CORRECT CODES.
 ALL WORK SHALL BE AS PER THE 5TH EDITION OF THE FBC
 2014 RATHER THAN THE SOUTH FLORIDA BLDG. CODE AS WELL
 AS THE 2011 EDITION OF THE NEC.
 3. CORRECT ELECTRICAL NOTE 7 AS ARTICLE 370 OF THE 2011
 NEC ADDRESSES CABLE BUS. THE ARTICLE ADDRESSING
 JUNCTION BOXES IS 314.
 4. PER NEC 406.12 ALL NEWLY INSTALLED RECEPTACLES IN
 DWELLING UNITS SHALL BE LISTED AS ?TAMPER-RESISTANT?.
 ADD THIS NOTE TO THE ELECTRICAL NOTES.
 5. PER NEC 250.94 THE INTER-SYSTEM BONDING TERMINAL
 SHALL BE AT THE SERVICE OR METER. CORRECT YOUR RISER
 DIAGRAM AS NOTED.
 6. PER NEC 210.70(A)(3) THE ATTIC LIGHT SWITCH SHALL BE
 ON A WALL ADJACENT TO THE POINT OF ENTRY. MAY I SUGGEST
 A SWITCH WITH A PILOT LIGHT TO INDICATE STATUS LOCATED
 IN A VISIBLE LOCATION.
 7. PER NEC 210.52(A) THE WALL BETWEEN THE CLOSET AND
 BATHROOM DOOR IS MISSING AN OUTLET.
 8. PER NEC 210.52(A) THE ROOM JUST OUTSIDE THE BEDROOM
 DOOR IS MISSING OUTLETS. MAY I SUGGEST A 3 WAY SWITCH
 FOR THE LIGHT AS WELL.
 9. PER NEC 680.73 THE POWER SOURCE OUTLET SHALL BE
 READILY ACCESSIBLE AND FACING THE OPENING IF
 APPLICABLE. THIS DEVICE SHALL BE NO MORE THAN 1 FOOT
 AWAY FROM THE OPENING.
 10. PER NEC 680.74 ALL METAL PARTS ASSOCIATED WITH OR
 IN CONTACT WITH THE CIRCULATING WATER SHALL BE BONDED
 WITH A #8 COPPER CONDUCTOR WHICH SHALL BE CONNECTED TO
 THE PUMP MOTOR AND FOR EQUIPOTENTIAL BONDING.
 11. PER NEC 440 PART II A DISCONNECT FOR THE MINI-SPLIT
 CONDENSING UNIT IS REQUIRED.
 12. PER FBC 314.3 YOU SHALL HAVE A SMOKE DETECTOR
 ?INSIDE? THE SLEEPING AREA AND ALSO IN THE IMMEDIATE
 AREA OUTSIDE. CORRECT THE DEVICE PLACEMENT AS INDICATED
 ON THE PLANS.
 13. PER FBC 314.3.1 YOU SHALL INSTALL SMOKE DETECTORS
 THROUGHOUT THE RESIDENCE AS REQUIRED FOR NEW
 CONSTRUCTION. IF ALREADY DONE SO, DISREGARD THIS
 COMMENT.
 14. PER FBC 315 IF THE RESIDENCE HAS AN ATTACHED GARAGE
 OR ANY FOSSIL FUEL BURNING APPLIANCE YOU SHALL INSTALL
 CARBON MONOXIDE DETECTORS AS INDICATED BY THIS SECTION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER