Plan Review Notes
Plan Review Notes For Permit 16060011
Permit Number 16060011
Review Stop B
Sequence Number 1
Notes
Date Text
2016-07-29 18:39:50RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. THE VALUATION WAS UPDATED TO $60,605. THE
 PERMIT FEE BALANCE IS $1569.47.
  
 3- SHEET S.P 1:
 A) THE COMPONENTS AND CLADDING DESIGN PRESSURES SHOWN
 ON THE DESIGN CRITERIA ARE TOO LOW. THEY DO NOT
 CORRESPOND TO EXPOSURE "C". REVISE AS REQUIRED. SEC.
 R301.2.1.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) ALTERATION LEVEL SPECIFIED ON THE DESIGN CRITERIA IS
 NOT ALTERATION LEVEL LL. THIS IS AN ADDITION. REVISE AS
 REQUIRED. SEC. 507 FBC-EXISTING BUILDING, 5TH EDITION
 (2014).
  
 4- REVISE COLUMN & BEAM SCHEDULE ON SHEET A-1. SIZE OF
 COLUMN C-1 IS NOT CLEAR. WHERE IS THE DIMENSION OF 16"
 TAKEN FOR THE 8" X 8" COLUMN?. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- SHEET A-2: IDENTIFY THE ROOMS THAT ARE ADJACENT TO
 THE ADDITION. IF THERE ARE ANY BEDROOMS ADJACENT TO THE
 ADDITION, THEN NEED TO SHOW COMPLIANCE WITH THE EGRESS
 REQUIREMENTS. SPECIFY WINDOWS TYPE AND SIZE TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS. SEC. 701.2
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 6- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOMS,
 INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC. R315
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- SHEET A-4: REVISE THE BOTTOM CORD LIVE LOAD
 SPECIFIED ON THE ROOF TRUSS DESIGN LOAD SHOWING
 COMPLIANCE WITH THE NOTES "A" AND "B" OF TABLE R301.5
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH TRUSS DRAWINGS
 SUBMITTED.
  
 8- THE NORTH ARROW ORIENTATION SHOWN IN ALL PLANS IS
 INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 9- ENERGY CALCULATIONS SUBMITTED;
 A) OWNER/AGENT TO CERTIFY AND DATE AT BOTTOM OF FORM
 SUBMITTED AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) COMPLETE ALL THE INFORMATION ON TOP OF FORM
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) REVISE THE ATTIC VENT RATIO SHOWN ON PAGE 2 OF 4.
 CODE REQUIRES 1/150 RATIO. SEE SEC. R806.2
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 D) THERE ARE NO INSULATED DOORS IN THE ADDITION. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH INFORMATION SHOWN ON THE PLANS FOR THE ADDITION.
 SEE WINDOW ORIENTATION AND NUMBER OF WINDOWS SHOWN ON
 PLANS FOR THE ADDITION AND REVISE. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 F) THE WINDOWS OVERHANG SEPARATION SHOWN ON PAGE 3 OF 4
 DOESN'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 G) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS WITH GLAZING SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN THE ENERGY
 CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT FACTOR
 FOR GLAZING.
  
 10- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 MECHANICALLY FASTENED, THEN SPECIFY SCREW OR NAIL
 TYPE/SIZE AND NUMBER OF SCREWS/NAILS PER TILE. IF
 SPECIFYING ADHESIVE, THEN PROVIDE PRODUCT APPROVAL. SEE
 ROOF TILE PRODUCT APPROVAL FOR REFERENCE.
  
 11-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED FOR
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA FOR LISTED ADHESIVES.
  
 B) ROOF TILE: THERE ARE TWO DIFFERENT NOA'S SUBMITTED
 FOR TWO DIFFERENT MANUFACTURER'S . NOA 15-1102.04 AND
 NOA 12-0207.02. SUBMIT ONLY THE ROOF TILE NOA THAT IS
 GOING TO BE INSTALLED.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST
 THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE
 SPECIFIED CONNECTOR.
  
 12- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 13- SHEET A-4: THE UPLIFT LOADS SHOWN ON THE ROOF
 FRAMING PLAN FOR THE TRUSS GIRDER A11G DON'T MATCH
 UPLIFT LOADS SHOWN ON THE TRUSS PACKAGE SUBMITTED. AND,
 THE CONNECTORS SPECIFIED ON THE CONNECTOR SCHEDULE
 DON'T MEET THE UPLIFT LOADS SPECIFIED FOR TRUSS GIRDER
 A11G ON TRUSS PACKAGE. REVISE AS REQUIRED. SEC. R301
 FBC-RESIDENTIAL.
  
 14- TRUSS PACKAGE SUBMITTED (NOTE: SUBMIT ONLY 2 COPIES
 OF TRUSS PACKAGE):
 A) TRUSS ENGINEER NEEDS TO PROVIDE ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 B) THE COVER PAGE IS MISSING THE INFORMATION OF THE
 STRUCTURAL ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-31.003
  
 C) STRUCTURAL ENGINEER OF RECORD TO REVIEW AND APPROVE
 COMPLETE TRUSS PACKAGE (LAYOUT AND INDIVIDUAL TRUSSES)
 PRIOR TO TO SUBMITTAL TO THIS OFFICE. SEC. 107.3.4.2
 CITY AMENDMENTS.
  
 ****PLEASE DO NOT STAPLE PRODUCT APPROVALS TO PLANS.
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW DRAWINGS.
 SUBMIT OLD PLANS FOR REFERENCE TO EXPEDITE THE REVIEW
 PROCESS.
  