| | ELECTRICAL PLAN REVIEW COMMENTS |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - NEC 210.12(A) ARC- FAULT PROTECTION REQUIRED IN ALL |
| | AREAS SPECIFIED UNDER THIS SECTION NOT JUST BEDROOMS, |
| | PLEASE CHANGE NOTE # 29 TO COMPLY WITH THIS CODE |
| | ARTICLE. |
| | - NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING |
| | UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, |
| | 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER |
| | RESISTANT RECEPTACLES. |
| | - R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE |
| | BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR |
| | WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED AND |
| | HAVING A FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A |
| | FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE, |
| | FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE AS |
| | BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 |
| | MM) OF EACH ROOM USED FOR SLEEPING PURPOSES.(VERIFY IF |
| | APPLICABLE) |
| | - MODIFY AND RE-CALCULATE THE LOAD CLACS IT SEEMS YOU |
| | WENT WITH THE OPTIONAL METHOD, THEREFORE WITH THE 3 VA |
| | FOR THE GENERAL LIGHTING , THE 2 SMALL APPLIANCE(1500 |
| | EACH) AND LAUNDRY CIRCUIT (1500), PLUS THE SUM OF THE |
| | NAMEPLATE RATING OF ELECTRICAL EQUIPMENT YOUR |
| | CALCULATIONS ARE UNDERSIZED THE DEMAND LOAD INCLUDING |
| | THE A/C HEAT ACCORDING TO YOUR INFORMATION CAME OUT TO |
| | BE 108 AMPS SO THE 100 AMP SERVICE IS INSUFFICIENT. THE |
| | RISER DIAGRAM WILL ALSO HAVE TO BE RE-ADJUSTED TO |
| | COMPLY WITH NEC 220.82(A)(B)(C) FEEDER AND SERVICE |
| | CALCULATIONS. |
| | - NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE |
| | AUGMENTED BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR |
| | PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR |
| | LESS. |
| | - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |