| 2016-06-03 18:51:49 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MAXIMUM WATER VELOCITY IN BRANCH SUCTION PIPING | | | IS 6 FEET PER SECOND WHEN ONE OF THE PAIR OF MAIN | | | DRAINS IS BLOCKED PER ANSI/APSP-7 2006. THE FLOW RATE | | | IN THE 2-1/2" SUCTION PIPE IS 7.64 FPS. THE 1 HP JANDY | | | FLOPRO VARIABLE SPEED PUMP HAS A MAXIMUM FLOW RATE OF | | | MORE THAN 120 GPM AT 20 FT OF HEAD PER THE PUMP CURVE | | | THAT WAS SUBMITTED. | | | |
|