| 2016-06-21 10:49:47 | 1) SHT. AN-1.0 - CODE REFERENCES - REFERENCE IS MADE TO |
| | THE 2001 WPB AMENDMENTS TO FBC. REVISE TO READ 2014 |
| | AMENDMENTS. |
| | 2) SHT.AN-3.0 - PLUMBING FIXTURE REQUIREMENTS - REFER |
| | TO TABLE 403.1 OF 2014 FLORIDA PLUMBING CODE. |
| | 3) IDENTIFY THE DIFFERENT OCCUPANCY AREAS ON THE PLAN. |
| | 4) THE OCCUPANT LOAD CALCULATIONS SHOW AN OCCUPANT LOAD |
| | OF 153 PERSONS AND THE PLUMBING FIXTURE REQUIREMENTS |
| | NOTES 297 PERSONS. CLARIFY. |
| | 5) THE WATER FILTRATION SYSTEM SHALL BE PROTECTED |
| | AGAINST CONTAMINATION PER 2014 FBC SEC.608.3. |
| | 6) SUBMIT FACTORY SIZING CALCULATIONS FOR THE GREASE |
| | TRAP & GREASE INTERCEPTOR. YOU CAN CONTACT LEE |
| | SCHNEEWEISS WITH SCHIER AT 1-800-538-4792. 2014 |
| | FBC-PLUMBING SEC.1003.2. |
| | 7) IS THIS A CHANGE OF OCCUPANCY? INDICATE ON THE |
| | PLANS. IF SO, ADDITIONAL REVIEW COMMENTS MAY BE |
| | GENERATED. |
| | 8) SHT. A-7.3 - THE ACCESSIBLE URRINAL SHALL BE MOUNTED |
| | WITH THE RIM LOCATED AT 17 INCHES ABOVE FINISH FLOOR, |
| | NOT 1'-7" AS SHOWN. 2014 FAC SEC. 605.2. |
| | 9) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE PER THE 2014 FAC SEC. 609.4. |
| | 10) SHT. P5.1 - THE SANITARY RISER SHOWS AN UNVENTED |
| | SINK (SK-1) DRAINING INTO THE TOP OF THE |
| | INTERCEPTOR.CLARIFY. |
| | 11) THE DISCHARGE OF THE INTEERCEPTORS ARE SHOWN AS |
| | INDIRECCT WASTES ON BOTH INTERCEPTORS. CLARIFY.ALSO, |
| | CLARIFY THE INLET CONNECTION TO THE AUTOMATIC GREASE |
| | INTERCEPTOR. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |