| 2016-06-15 08:02:28 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16051290 |
| | ADD: 701 S. ROSEMARY AVE. SUITE : 101 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 856-6655/ NEYITA LEIVA |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JUNE 14/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) AN-1.0 PROJECT INFORMATION/ CODE REFERENCES |
| | 1A) 2001/2004 W. P. B. AMENDMENTS ARE NO LONGER IN |
| | AFFECT, THEY SUNDOWN WITH THE ADOPTION OF THE NEWLY |
| | ADOPTED W. P. B. AMENDMENTS. 2010 W. P. B. AMENDMENTS |
| | ARE STILL IN AFFECT. |
| | |
| | 1B) THE UNSAFE BUILDING ABATEMENT CODE: IS A P. B. |
| | COUNTY CODE NOT A CITY OF WEST PALM BEACH ORDINANCE. |
| | |
| | 1C) ULDC ARTICLE 18 FLOOD DAMAGE PREVENTION IS ALSO A |
| | PALM BEACH COUNTY DOCUMENT THAT DOES NOT PERTAIN TO THE |
| | CITY OF WEST PALM BEACH. THIS JOBSITE IS NOT LOCATED IN |
| | AN A FLOOD ZONE. |
| | |
| | 1D) THE CODE REFERENCE FORM THE 2014 FBC-B FIGURE 1609C |
| | ULTIMATE WIND SPEEDS RISK CATEGORY I BUILDINGS. PLEASE |
| | NOTE THIS WIND DESIGN OF 160 VULT IS FOR BUILDINGS SUCH |
| | AS AGRICULTURAL OUT BUILDINGS (BARNS), MINOR STORAGE |
| | BUILDINGS AND SCREEN ENCLOSURES, 2014 FBC-B TABLE |
| | 1604.5. RISK CATEGORY OF BUILDINGS AND OTHER |
| | STRUCTURES. THIS BUILDINGS RISK CATEGORY SHOULD BE RISK |
| | CATEGORY II, FIGURE 1609B AND A VULT WIND SPEED OF 170 |
| | VULT. THE STRUCTURAL SHEET S-1.0 DOES HAVE THE CORRECT |
| | WIND DESIGN CRITERIA. |
| | |
| | 2) THE DETAILS ON SHEET S-3.0 DETAILS 2 & 3 BOTH |
| | INDICATE THE USE OF POLYSTYRENE STRUCTURAL FOAM. THE |
| | SUBMITTED DETAILS ONLY SHOW THE FOAM BEING ENCASED IN |
| | ONE DIRECTION. PLEASE PROVIDE A CROSS SECTION 90 |
| | DEGREES OF THOSE SHOWN, SHOWING THE FOAM BEING FULLY |
| | ENCASED BY THE CONCRETE, SEE FBC-B 2603.4.1.1. |
| | |
| | 3A) SHEETS AN-3.0, A-2.1 & A-5.0 ALL OF THESE SHEETS |
| | SHOW THE FLOOR PLAN WITH THE FURNITURE, NONE SHOW |
| | COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE SECTION 226.1 |
| | GENERAL. WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 3B) SHEETS AN-3.0, A-2.1 & A-5.0 ALL OF THESE SHEETS |
| | SHOW THE FLOOR PLAN WITH THE FURNITURE, NONE SHOW |
| | COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE SECTION 226.2 |
| | DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED |
| | TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE |
| | SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK |
| | SURFACES. PLEASE NOTE INCLUDE THE SEASONAL SEATING AS |
| | WELL AS THE SEATING AT FN-13. |
| | |
| | 3C) SHEETS AN-3.0, A-2.1 & A-5.0 ALL OF THESE SHEETS |
| | SHOW THE FLOOR PLAN WITH THE FURNITURE, NONE SHOW |
| | COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE SECTIONS: |
| | 3C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 3C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND |
| | 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 4) SHEET A-7.4 SHOWS THE LAYOUT OF THE SMALL CAF?. |
| | DETAIL (8) AN ELEVATION SHOWS AN ELEVATION OF 3 FT. 6 |
| | INCHES FOR THE BAR SEATING, BUT THE DETAIL FOR THE |
| | ACCESSIBLE SEATING DOES NOT SHOW THE HEIGHT OF THE |
| | ACCESSIBLE TOP. PLEASE SHOW COMPLIANCE WITH 2014 |
| | FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 5) SHEET A7.1 DETAIL # 6 RAMP ELEVATION & HANDRAILS. |
| | THE HANDRAILS ARE MISSING THE HORIZONTAL EXTENSION AT |
| | THE TOP AND BOTTOM OF THE RAMP. SEE THE 2014 |
| | FBC-ACCESS. CODE 505.10.1 & FIGURE 505.10.1. |
| | |
| | 6A) SHEET A-8.0 DETAILS SHOW THE USE OF STEEL TUBES IN |
| | THE HEADER AND SILL DESIGN WHERE AS THE STRUCTURAL |
| | SHEET S-3.0 DETAIL # 1 SHOWS THE USE OF A CONCRETE SILL |
| | AND CONCRETE LINTEL AND STEEL. DISCREPANCY IN PLANS, |
| | 107.2.1.3. ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 6B) SHEET S-3.0 DETAIL # 1 INDICATES THE USE OF A |
| | LINTEL WITH CONCRETE W NUMBER 4 STIRRUPS AT 4 INCHES ON |
| | CENTER, W 2 # 5S ON TOP AND BOTTOM. IS THIS A |
| | PRE-MANUFACTURED LINTEL, OR A POUR IN PLACE BEAM? |
| | 107.2.1.3. ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 7) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (G) ROOF TOP CURBS, PRE-ENGINEERED A/C STANDS |
| | |
| | 8) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 9) PROVIDE ENGINEERED DETAILS FOR MOUNTING OACU-1 CURB |
| | TO THE ROOF STRUCTURE AND THE UNIT TO THE CURB. |
| | 2014 FBC-B 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| | STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| | DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| | INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| | COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL |
| | PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| | THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS? |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 9) PLEASE INDICATE IF THIS PERMIT IS FOR A CHANGE OF |
| | OCCUPANCY TO AN A2 OCCUPANCY. IF SO PLANS ARE TO BE |
| | SUBMITTED TO P.B.C. IMPACT FEE OFFICE FOR IMPACT FEE |
| | ASSESSMENT. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |