| 2016-06-23 08:15:39 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:16051235 |
| | ADD: 880 VALLEY FORGE RD. |
| | CONT: FLORIDA DESIGN DRILLING CORP. |
| | TEL: 561-844-2966 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 23/2016 |
| | ACTION: DENIED |
| | |
| | |
| | 1) PLEASE NOTE SHEET S-2 INDICATES UNDER NOTE # 1 THIS |
| | IS A PRE-MANUFACTURERED BUILDING. PRE-MANUFACTURED |
| | BUILDINGS ARE BUILT AT A PLANT TOTALLY COMPLETE. FOR |
| | MANUFACTURERED BUILDINGS (MODULAR)AT A PLANT AND |
| | TRANSPORTED COMPLETE TO THE JOBSITE, THEY HAVE TO BE |
| | PART OF THE STATE MANUFACTURED BUILDING PROGRAM IN |
| | COMPLIANCE WITH : |
| | FLORIDA STATUTE 428.3 INSPECTIONS. INSPECTION OF |
| | INSTALLATION OF MANUFACTURED BUILDINGS AND CONSTRUCTION |
| | ACTIVITIES CONDUCTED AT THE SITE OF THE INSTALLATION |
| | SHALL BY CONDUCTED PURSUANT TO CHAPTER 1 HEREOF. |
| | INSPECTIONS DURING THE MANUFACTURING PROCESS SHALL BE |
| | CONDUCTED BY THOSE THIRD-PARTY AGENCIES |
| | |
| | THIS BUILDING IS SITE BUILT W/ OFF SITE |
| | PRE-MANUFACTURED PANELS. PLEASE CORRECT THE |
| | TERMINOLOGY. THE ISSUE WE HAVE WITH THIS BUILDING IS ON |
| | SHEET S-1 NOTES INDICATE FABRICATION AND ERECTION |
| | DRAWINGS WILL BE PREPARED BY A DELEGATE ENGINEER. |
| | |
| | WHAT WE ARE NOT GETTING IS THE INSPECTION OF THE STEEL |
| | (REBAR) AND EMBEDS IN THE STRUCTURAL WALL AND ROOF |
| | PANEL OR PANELS. THIS NEEDS TO BE COMPLETED BY A STATE |
| | CERTIFIED BUILDING INSPECTOR WHO HOLDS A BN LICENSE. |
| | THIS IS NOT A MODULAR BUILDING UNDER THE STATE PROGRAM. |
| | FLORIDA STATUTE 428.3 INSPECTIONS. INSPECTION OF |
| | INSTALLATION OF MANUFACTURED BUILDINGS AND CONSTRUCTION |
| | ACTIVITIES CONDUCTED AT THE SITE OF THE INSTALLATION |
| | SHALL BY CONDUCTED PURSUANT TO CHAPTER 1 HEREOF. |
| | INSPECTIONS DURING THE MANUFACTURING PROCESS SHALL BE |
| | CONDUCTED BY THOSE THIRD-PARTY AGENCIES FLORIDA ADMIN. |
| | CODE CHAPTER 61-41 MANUFACTURERED BUILDINGS. |
| | |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW BEFORE BEING SUBMITTED TO |
| | THE BUILDING DEPARTMENT. |
| | |
| | 2) ALL ONSITE WELDING OF EMBEDS TO PANEL SYSTEMS EITHER |
| | WALL OR ROOF PANELS WILL NEED TO BE COMPLETED BY A |
| | CERTIFIED WELDER, PLEASE PROVIDE PAPERWORK INDICATING |
| | THEIR CERTIFICATION. |
| | |
| | 3) PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (C) PANEL WALLS: WALL LOUVERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 4) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 5) SHEET S2 THE WALL INTERIOR ZONE # 4 PRESSURES ARE IN |
| | VULT PLEASE PROVIDE THE PRESSURES IN VASD SINCE THE |
| | PRODUCT APPROVALS ARE ALL IN VASD. 2014 FBC-B 1609.3.1 |
| | WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 6) SHEET S2 SHOWS COMPONENT AND CLADDING PRESSURES FOR |
| | THE WALL ZONES BUT THERE ARE NO PRESSURES FOR THE FLAT |
| | CONCRETE ROOF ZONES 1, 2 NOR 3. 2014 FBC-B 1603.1.4 |
| | WIND DESIGN DATA. PLEASE CONVERT PRESSURES TO VASD. |
| | 2014 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |