| 2016-06-03 14:18:12 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT 16051222 | | | 6/3/16 | | | | | | 1) CLARIFY HOW THE AC SYSTEM WAS SIZED- PROVIDE | | | CALCULATIONS. | | | | | | 2 PLEASE REFER TO SECTION 414.1.3 FBC-14 BUILDING AND | | | SUBMIT THE REQUIRED REPORT FOR THE SODIUM HYPOCHLORITE | | | AND ALL OTHER CHEMICALS TO BE STORED ON USED FOR | | | PROCESSING IN THE BUILDING. PLEASE NOTE THAT A | | | HAZARDOUS EXHAUST VENTILATION SYSTEM MAY BE REQUIRED- | | | SEE SECTION 510 FBC-14 MECHANICAL FOR CODE | | | REQUIREMENTS. | | | | | | 3) PROVIDE SUBMITTALS FOR THE SODIUM HYPOCHLORITE TANK, | | | AND THE PROCESS PIPING, VALVES, AND FITTINGS WITH SHOP | | | DRAWING APPROVAL SIGNATURES FROM THE DESIGN | | | PROFESSIONAL OF RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|