2016-08-01 17:00:25REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) 2ND REQUEST, PROVIDE INTERSYSTEM BONDING TERMINAL
 PER NEC 250.94 / FBC-R SECTION E3609.3
  
 2) 2ND REQUEST, ADD A NOTE FOR FBC-E R404.1 A MINIMUM
 OF 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY
 LAMPS.
  
 3) OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE
 VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS. NEC 240.24(D) / FBC-R SECTION E3705.7
 (RELOCATE ACCORDINGLY)
  
 4) RISER DIAGRAM REFLECTS THE FOLLOWING DEFFICIENCIES
 FBC 107 MINIMUM PLAN REVIEW
 A- LABEL FPL METER ENCLOSURE WITH AMPERE RATING
 B- 250 AWG MCM WIRE MUST BE USED UP TOO THE FIRST
 DISCONNECTING MEANS THAT CARRIES THE ENTIRE LOAD
 C- CLARIFY HOW EXISTING SUB PANELS ARE BEING FED WITH A
 3/4'' CONDUIT. VERIFY ANNEX C BECAUSE CONDUIT FILL
 DOESN'T CORRELATE.
  
 5) PANEL SCHEDULE REFLECTS THE FOLLOWING DEFFICIENCIES
 FBC 107 MINIMUM PLAN REVIEW
 A- PANEL #1 200 AMP BUS RATING IS BEING EXCEEDED PLEASE
 MODIFY ACCORDINGLY NEC 408.36(A)
 B- SCHEDULE #1 HAS INCORRECT BREAKERS PROTECTING SUB
 PANELS, LOOK AT CIRCUIT # 2,4 & CIRCUIT # 14,16
  
 6) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.