| Date |
Text |
| 2016-08-01 17:00:25 | REVIEW 2014 5TH FBC ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) 2ND REQUEST, PROVIDE INTERSYSTEM BONDING TERMINAL |
| | PER NEC 250.94 / FBC-R SECTION E3609.3 |
| | |
| | 2) 2ND REQUEST, ADD A NOTE FOR FBC-E R404.1 A MINIMUM |
| | OF 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A |
| | MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY |
| | LAMPS. |
| | |
| | 3) OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE |
| | VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN |
| | CLOTHES CLOSETS. NEC 240.24(D) / FBC-R SECTION E3705.7 |
| | (RELOCATE ACCORDINGLY) |
| | |
| | 4) RISER DIAGRAM REFLECTS THE FOLLOWING DEFFICIENCIES |
| | FBC 107 MINIMUM PLAN REVIEW |
| | A- LABEL FPL METER ENCLOSURE WITH AMPERE RATING |
| | B- 250 AWG MCM WIRE MUST BE USED UP TOO THE FIRST |
| | DISCONNECTING MEANS THAT CARRIES THE ENTIRE LOAD |
| | C- CLARIFY HOW EXISTING SUB PANELS ARE BEING FED WITH A |
| | 3/4'' CONDUIT. VERIFY ANNEX C BECAUSE CONDUIT FILL |
| | DOESN'T CORRELATE. |
| | |
| | 5) PANEL SCHEDULE REFLECTS THE FOLLOWING DEFFICIENCIES |
| | FBC 107 MINIMUM PLAN REVIEW |
| | A- PANEL #1 200 AMP BUS RATING IS BEING EXCEEDED PLEASE |
| | MODIFY ACCORDINGLY NEC 408.36(A) |
| | B- SCHEDULE #1 HAS INCORRECT BREAKERS PROTECTING SUB |
| | PANELS, LOOK AT CIRCUIT # 2,4 & CIRCUIT # 14,16 |
| | |
| | 6) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |