Plan Review Notes
Plan Review Notes For Permit 16051216
Permit Number 16051216
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-25 11:47:29CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE ON PLANS GRILL SIZES AND TOTAL CFM OF ALL
 EXISTING ROOMS.
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S
 BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE
 WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING
 LOADS FOR THE DIRECTIONAL ORIENTATION OF THE BUILDING.
 THE MANUFACTURER AND MODEL
 NUMBER OF THE OUTDOOR AND INDOOR UNITS (IF SPLIT
 SYSTEM) SHALL BE SUBMITTED ALONG
 WITH THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE
 DESIGN CONDITIONS DESCRIBED IN
 SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER
 SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 (2) PROVIDE ON EQUIPMENT SCHEDULE THE MANUFACTURER AND
 MODEL NUMBER OF THE OUTDOOR AND INDOOR UNITS.
 (3) THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE
 DESIGN CONDITIONS DESCRIBED IN
 SECTION R302.1.
 (4) CFM TOTAL OF AHU.
 (5) SEER
 (6) AHRI OF EQUIPMENT ON PLANS.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved