| 2016-06-13 10:40:56 | JOB PERMIT NUMBER: 16051216 |
| | JOB ADDRESS: 520 51 STREET |
| | WEST PALM BEACH FLORIDA |
| | DATE: JUNE 13 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED. NEC 250.56 SERVICE GROUNDING ELECTRODE TO BE |
| | AUGMENTED BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR |
| | PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR |
| | LESS. |
| | - FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICACY LAMPS. ADD A NOTE. |
| | - FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. ADD A NOTE. |
| | - LOAD CALCS ARE MISSING POOL AND SPRINKLER PUMP PLEASE |
| | INCLUDE, FURTHERMORE ACCORDING TO OUR ?PROPERTY |
| | APPRAISAL? INFORMATION THE AREA UNDER AIR IS 1777 SQ |
| | FT. RE-CALCULATE AND ADJUST ACCORDINGLY. NEC |
| | 220.82(B)(1)(2)(3)(4) |
| | - PANEL SCHEDULE REFLECTS THE 100 AMP SUB PANEL BEING |
| | FED WITH A # 10 AWG AND A 30 AMP OCPD ? NEC 210.19, |
| | 210.20 (RATINGS) |
| | - NEC 408.36 A PANELBOARD SHALL BE PROTECTED BY AN |
| | OVERCURRENT PROTECTIVE DEVICE HAVING A AMPACITY RATING |
| | NOT GREATER THAN THAT OF THE PANELBOARD. EXPLAIN HOW |
| | YOUR COMING OFF A 200 A PANEL TO A 125 DISCONNECT TO |
| | PROTECT A 100 AMP PANELBOARD ? |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |