| Plan Review Notes For Permit 16051209 |
| Permit Number |
16051209 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-01 13:35:00 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE CLARIFY IF THERE IS A NEW A/C COMPRESSOR | | | BEING INSTALLED ALONG WITH THE NEW AHU SHOWN. ALSO | | | PROVIDE EXISTING PANEL RATING AND A REVISED PANEL LOAD | | | CALCULATION TO DETERMINE IF PANEL IS ADEQUATE TO | | | WITHHOLD NEW EQUIPMENT. FBC 107.3.5 MINIMUM CRITERIA | | | PLAN REVIEW. | | | 2.CLARIFY IF THERE IS A MECHANICAL PERMIT FOR AHU. IF | | | SO PROVIDE PERMIT NUMBER ISSUED | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|