Plan Review Notes For Permit 16051209
Permit Number 16051209
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-01 13:35:00INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY IF THERE IS A NEW A/C COMPRESSOR
 BEING INSTALLED ALONG WITH THE NEW AHU SHOWN. ALSO
 PROVIDE EXISTING PANEL RATING AND A REVISED PANEL LOAD
 CALCULATION TO DETERMINE IF PANEL IS ADEQUATE TO
 WITHHOLD NEW EQUIPMENT. FBC 107.3.5 MINIMUM CRITERIA
 PLAN REVIEW.
 2.CLARIFY IF THERE IS A MECHANICAL PERMIT FOR AHU. IF
 SO PROVIDE PERMIT NUMBER ISSUED
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  