| 2016-08-17 13:51:43 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1) ORIGINAL PLANS WERE PASSED WITH SEVERAL PROVISO'S | | | THAT WEREN'T ADDRESSED IN THE 2ND SUBMITTAL PLEASE ADD | | | THE FOLLOWING NOTES: | | | 1A) AFCI PROTECTION REQUIRED PER NEC 210.12[B] | | | 1B) TAMPER RESISITANT RECEPTACLES REQUIRED PER NEC | | | 406.12 | | | 1C) SMOKE ALARMS REQUIRED PER FBC-R 314 & 315 | | | | | | 2) LABEL METER ENCLOSURE "METER MAIN" TO COMPLY WITH | | | NEC 230.70[A][1] DISCONNECTING MEANS OF SERVICE | | | CONDUCTORS SHALL BE LOCATED AT A READILY ACCESSIBLE | | | LOCATION NEAREST THE POINT OF ENTRANCE. | | | | | | 3) CORRECT GROUNDING DETAILS TO A # 4 CU ELECTRODE | | | CONDUCTOR PLUS AUGMENTATE A ROD OR COMPLY WITH PROVING | | | 25 OHMS TO GROUND. NEC 250.56. ADD AN INTERSYSTEM | | | BONDING TERMINAL IN ACCORDANCE WITH NEC 250.94 | | | | | | 4) CLARIFY PANEL LOCATION ? IS IT IN A CLOTHES CLOSET ? | | | DOES THE WORKING SPACE HEIGHT SUFFICE THE 6.5' FROM | | | FLOOR REQUIREMENT ? NEC 110.26 WORKING CLEARANCE & | | | FBC-R SECTION E3405 | | | | | | 5) PLEASE TRY TO DARKEN IN THE ELECTRICAL POINTS ON THE | | | FLOOR PLAN FOR THE QUALITY OF THE EXAMINER REVIEW. | | | FBC-107 MINIMUM PLAN REVIEW | | | | | | - PERMIT # 16051207, 523 28TH STREET WPB FLORIDA. [ | | | FRONT BUILDING ] |
|