Plan Review Notes
Plan Review Notes For Permit 16051191
Permit Number 16051191
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-06 14:13:31JOB PERMIT NUMBER: 16051191
 JOB ADDRESS: 1801 S FLAGLER DRIVE SUITE # 305
 WEST PALM BEACH FLORIDA
 DATE: JUNE 6 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 - SHOW KITCHEN COUNTERTOPS RECEPTACLE OUTLETS AS BEING
 GFCI PROTECTED IN ACCORDANCE WITH NEC 210.8(A)
 - FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 - FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS.
 - NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL.
 - NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT. OR
 MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. (DOUBLE CHECK
 MASTER, GUEST ROOM, LIVING/DINING, AND ENTRANCE.)
 - FBC-E 808.3.1 ENCLOSED AREAS. ALL ENCLOSED AREAS,
 OTHER THAN CLOSETS, KITCHENS, BASEMENTS, GARAGES,
 HALLWAYS, LAUNDRY AREAS, UTILITY AREAS, STORAGE AREAS
 AND BATHROOMS SHALL HAVE A MINIMUM OF TWO DUPLEX
 RECEPTACLE OUTLETS OR ONE DUPLEX RECEPTACLE OUTLET AND
 ONE CEILING OR WALL-TYPE LIGHTING OUTLET.( EXCEPTION TO
 WALL SPACE REQUIREMENT )
 - PANEL SCHEDULE REFLECTS INCORRECT OCPD & WIRE SIZES
 FOR EXAMPLE THE RANGE SHOWS 1500 VA ON A 50 AMP BKR ?,
 THE W/H SHOWS 1000 VA ON A 20 AMP BKR ?, THE OVEN 1500
 VA ON A 15 AMP BKR?, ALL SINGLE POLE ?, UNLESS THESE
 ARE GAS PLEASE REVISE. KEEP IN MIND CODE REQUIRES
 MINIMUM A 20 AMP CIRCUIT FOR THE BATHROOM WHICH ISN?T
 PROVIDED NEC 210.11(C)(3).
 - IN ACCORDANCE WITH NEC 220.82(A)(B) THE CALCULATION
 MUST INCLUDE THE MINIMUM OF GENERAL LIGHTING LOAD(3 VA
 X SQ FT), 2 SMALL APPLIANCE 1500 VA EACH AND 1 LAUNDRY
 1500 VA UNLESS FACILITIES ARE PROVIDED SEPARATELY, PLUS
 THE NAME PLATE OF OTHER EQUIPMENT AND AC VS HEAT LOADS.
 PLEASE VERIFY ?
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  