| Plan Review Notes For Permit 16051150 |
| Permit Number |
16051150 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-27 18:43:02 | BUILDING REVIEW COMMENTS TO REVISION SUBMITTED TO | | | ADDRESS PROVISO DATED 05/10/16: | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | | A) NEW OVERHEAD GARAGE DOORS AS SHOWN ON PLANS. | | | RESPONSE: NOT ADDRESSED. NO PRODUCT APPROVAL SUBMITTED | | | AT THIS TIME. | | | | | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS. | | | RESPONSE: OK. | | | | | | 2- ARCHITECT TO REVIEW/APPROVE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.34.1 CITY AMENDMENTS. | | | RESPONSE: THIS APPLIES TO GARAGE DOORS. NO PRODUCT | | | APPROVAL SUBMITTED YET. | | | | | | ORIGINAL COMMENT: | | | 3- PROVIDE COMPLETE FRAMING DETAIL FOR THE INSTALLATION | | | OF TWO OVERHEAD GARAGE DOORS INSTEAD OF ONE AS SHOWN ON | | | PLANS. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. | | | R301.1 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | RESPONSE: REVISED DRAWING DOESN'T SPECIFY THE | | | STRUCTURAL CONNECTORS OF ALL THE FRAMING MEMBERS OF THE | | | NEW GARAGE DOORS. PROVIDE COMPLETE FRAMING DETAILS AND | | | SPECIFICATIONS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|