| 2016-05-31 16:59:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET A 1 - THERE IS NO INDICATIONS OF REVIEW AND/OR |
| | COMPLIANCE WITH ANY FIRE CODE. |
| | |
| | ENSURE A REVIEW AND PROVIDE A NOTE: |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | |
| | 2) SHEET A 2 - THERE IS NO INDICATIONS OF ANY EXISTING |
| | FIRE SPRINKLER OR FIRE ALARM PROTECTION |
| | |
| | PROVIDE A NOTE INDICATING ANY EXISTING LIFE SAFETY |
| | EQUIPMENT/DEVICESAS APPLICABLE. |
| | |
| | |
| | 3) SHEET A 3 - THE SHEET IS INDICATING "EXISTING FLOOR |
| | PLAN". SHEET A 2 IS INDICATING THE SAME. |
| | |
| | PROVIDE ACCURATE SHEET IDENTIFICATION I.E. |
| | "PROPOSED/NEW FLOOR PLAN". |
| | |
| | 4) SHEET A 3 - ANY REMOVAL AND/OR CONSTRUCTION OF WALLS |
| | AND /OR CEILINGS REQUIRE AN EVALUATION OF THE FIRE |
| | ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND |
| | COMPLIANCE BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | PROVIDE A NOTE: |
| | |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |