| 2016-06-02 17:07:22 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16051142 |
| | ADD: 400 N. FLAGLER DR. SUITE # 805 |
| | CONT: SMART CHOICE CONSTRUCTION INC. |
| | TEL: 561-317-3600 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 02/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 CODE INFORMATION: |
| | |
| | 1A) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2014 |
| | ALTERATIONS RESIDENTIAL. THE COVERSHEET SHOULD READ THE |
| | DESIGN IS TO THE 2014 FBC-BUILDING CODE AND THE 2014 |
| | EXISITING BUILDING CODE, THE 2014 FBC-RESIDENTIAL IS |
| | FOR 1 & 2 FAMILY ONLY NOT A R2 CONDO. |
| | |
| | 1B) THE PLANS ALSO STATE THE DESIGN: TABLE 601 BUILDING |
| | TYPE VB. NOTE THIS IS A 24 STORY R2 HIGHRISE. PLEASE |
| | REFER TO THE 2014 FBC-B TABLE503 AND BUILDING TYPE; IA |
| | PLEASE CORRECT PLANS. |
| | |
| | 1C) SCOPE OF WORK DOES NOT INCLUDE ANY REMOVAL AND |
| | REPLACEMENT OF EXTERIOR DOORS & WINDOWS. SHEET A-2 AND |
| | A-3 INDICATE THE REMOVAL AND REPLACEMENT OF THESES |
| | ELEMENTS. 107.2.1.3 . |
| | |
| | 2) DISCREPANCY IN PLANS, SHEET A2 IS INDICATED AS |
| | EXISITNG FLOOR PLAN AND SHEET A3 ALSO INDICATES |
| | EXISITNG FLOOR PLAN BUT APPEARS TO BE PROPOSED |
| | MODIFICATIONS TO THE R2 CONDOMINIUM. 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. APPEARS TO BE A TYPO. |
| | |
| | 3) SHEET A3 INDICATES NEW EXTERIOR DOOR AND WINDOWS. |
| | PLEASE PROVIDE PRODUCT APPROVALS FOR COMPLIANCE WITH: |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 5A) STRUCTURAL DESIGNS, MWFRS & COMPONENTS AND CLADDING |
| | BY JAIRO GONZALEZ P. E. INDICATE THEY WERE COMPLETED |
| | FOR AN EXPOSURE C WHERE AS THE JOBSITE LOCATION IS |
| | CONSIDERED A D EXPOSURE, BOTH TO THE NOTHEAST AND |
| | SOUTHEAST A VECTOR OR RAY CAN TRAVEL OVER 6,000 FT |
| | BEFORE HITTING LAND. 2014 FBC-B 1609.4.3 EXPOSURE |
| | CATEGORIES.EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE |
| | GROUND SURFACE ROUGHNESS, AS DEFINED BY SURFACE |
| | ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION FOR A |
| | DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 TIMES |
| | THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER. |
| | |
| | 5B) THE OTHER ISSUE IS THE CALCULATIONS ARE ALSO TAKEN |
| | AT 80 FT. THE BUILDING IS A 24 STORY HIGHRISE. THE |
| | NEGATIVE PRESSURES ARE ALWAYS TAKEN FROM THE ROOF. QH. |
| | ASCE7-10. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | STRUCTURAL CALCULATIONS |
| | |