| Plan Review Notes For Permit 16051137 |
| Permit Number |
16051137 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-16 13:06:52 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - SHOW LOCATIONS OF THE KITCHEN COUNTERTOP AND BATH | | | GFCI RECEPTACLES ON FLOOR PLANS FBC 107. NEC | | | 210.52(C)(1) WALL COUNTERTOP SPACES.NEC 210.520(D) | | | BATHROOMS. | | | | | | - ADD A NOTE FOR TAMPER RESISTANT RECEPTACLES AND | | | ARC-FAULT PROTECTION IN ACCORDANCE WITH NEC 210.12(B) & | | | NEC 406.12 | | | | | | - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS | | | 314 AND 315 PLEASE SHOW EACH DEVICE LOCATION ON THE | | | FLOOR PLANS TO COMPLY. | | | | | | |
|