2016-06-16 13:06:52REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - SHOW LOCATIONS OF THE KITCHEN COUNTERTOP AND BATH
 GFCI RECEPTACLES ON FLOOR PLANS FBC 107. NEC
 210.52(C)(1) WALL COUNTERTOP SPACES.NEC 210.520(D)
 BATHROOMS.
  
 - ADD A NOTE FOR TAMPER RESISTANT RECEPTACLES AND
 ARC-FAULT PROTECTION IN ACCORDANCE WITH NEC 210.12(B) &
 NEC 406.12
  
 - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS
 314 AND 315 PLEASE SHOW EACH DEVICE LOCATION ON THE
 FLOOR PLANS TO COMPLY.
  
  