| 2016-06-21 19:00:50 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PRODUCT APPROVALS FOR THE FRENCH DOORS DO NOT |
| | SPECIFY ANY ANCHORS FOR ATTACHING TO THE 2" X 4" |
| | ALUMINUM TUBE MULLION. THE ENGINEER WILL HAVE TO |
| | SPECIFY THE ANCHORS AND SPACING THAT WILL PROVIDE AN |
| | EQUIVALENT CONNECTION. SEE SHEET 10 OF THE FRENCH DOOR |
| | PRODUCT APPROVAL DRAWINGS. FBC-R301.1 |
| | |
| | 2) THE ENGINEER'S PLANS SPECIFY 3" THICK EPS FOAM CORE |
| | WALL PANELS WITH 0.060" (14GA.) ALUMINUM SKINS. THE |
| | PRODUCT APPROVAL THAT WAS SUBMITTED (FL19974) IS FOR 4" |
| | AND 6" THICK EPS FOAM CORE WALL PANELS WITH 26 GAUGE |
| | STEEL SKINS. PLEASE COORDINATE THE PRODUCT APPROVALS |
| | AND THE PLANS. FBC 107.2.1 |
| | |
| | 3) THE ANCHORS THAT WILL CONNECT THE CHANNELS TO THE |
| | CONCRETE FLOOR, WALL AND TIE BEAM ARE NOT SPECIFIED ON |
| | THE PLANS. ON SECTIONS A AND D THE ANCHORS ARE TAGGED |
| | WITH NUMBER 6, WHICH IS THE NOTE FOR THE SHOP WELD FOR |
| | THE BASE AND CAP PLATES ON THE ALUMINUM TUBE MULLION. |
| | FBC 107.2.1 ON SHEET 2 OF FL19974, 5/8" DIA. J-BOLTS |
| | ARE SPECIFIED TO ANCHOR THE BOTTOM CHANNEL. |
| | |
| | 4) SHEET 2 OF THE PRODUCT APPROVAL (FL19974) SPECIFIES |
| | THAT THE STRUCTURAL PANELS ARE ATTACHED TO THE CHANNEL |
| | WITH SCREWS ON BOTH SIDES. |