| Plan Review Notes For Permit 16051101 |
| Permit Number |
16051101 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-10 07:23:25 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16051101 | | | 6/10/11 | | | | | | 1) SHEET M0.1: THE DIGITAL SIGNATURE ON THIS SHEET HAS | | | A PROCESS ERROR THAT NEEDS TO BE CORRECTED. | | | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. SEE | | | SHEET ALS.1.1 CODE DATA AND ADD THE LEVEL OF ALTERATION | | | PER THE FLORIDA EXISTING BUILDING CODE 2014. | | | | | | 3) M2.1: PLEASE ENLARGE THE PRINT ON THE VAV BOXES- IT | | | APPEARS THAT THE NUMBER ID'S ON THE BOXES DO NOT MATCH | | | THE VAV TAG LABELS. | | | | | | 4) M6.1: PROVIDE THE SCOP RATING OF THE NEW CARRIER | | | MINI-SPLIT SYSTEM- SEE TABLE C403.2.3(10) FBC-14 ENERGY | | | CONSERVATION. | | | | | | 5) SHOW THE LOCATION OF THE ROOFTOP CONDENSER AND | | | PROVIDE TIE-DOWN ENGINEERING FOR THE STAND AND THE CU- | | | SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|