| 2016-06-09 15:47:26 | JOB PERMIT NUMBER: 16051101 |
| | JOB ADDRESS: 501 S FLAGLER DR SUITE #600 |
| | WEST PALM BEACH FLORIDA |
| | DATE: JUNE 9 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - GENERAL COMMENT, ALL LOW VOLTAGE AND FIRE ALARM SHALL |
| | BE SUBMITTED UNDER A SEPARATE PERMIT. |
| | - E0.1 ADD A NOTE, NEC 110.16 ARC-FLASH HAZARD WARNING |
| | LABELS & NEC 110.24 MAXIMUM AVAILABLE FAULT CURRENT |
| | MARKING REQUIRED, BOTH IDENTIFICATIONS SHALL BE |
| | SUITABLE FOR THE ENVIRONMENT INVOLVED. |
| | - E2.1 NEC 110.26(D) ILLUMINATION SHALL BE PROVIDED FOR |
| | ALL WORKING SPACES ABOUT ELECTRICAL EQUIPMENT, |
| | SWITCHBOARDS, AND PANELBOARDS. NO LIGHTS SHOWN BY |
| | PANELS ? |
| | - E3.1 NEC 300.3(C)(1) ALL CONDUCTORS SHALL HAVE AN |
| | INSULATION RATING EQUAL TO AT LEAST THE MAXIMUM CIRCUIT |
| | VOLTAGE APPLIED TO ANY CONDUCTOR WITHIN THE ENCLOSURE, |
| | CABLE, OR RACEWAY. (UNLESS SEPARATED BY BARRIERS IN |
| | ACCORDANCE TO NEC 725) APPLIES TO CONFERENCE ROOM TABLE |
| | INSTALLATIONS. |
| | - E5.1 PROVIDE EXISTING AIC & SCR OF OCPD AND |
| | ELECTRICAL APPARATUS PER NEC 110.9,110.10. EXISTING |
| | RISER DIAGRAM TO SHOW CONDUIT, WIRE, AND MAIN |
| | PROTECTION SIZES FROM BUS-DUCT DISCONNECT TO EXISTING |
| | TRANSFORMER. (SHOW TRANSFORMER KVA RATING AS WELL). FBC |
| | 107 MINIMUM PLAN CRITERIA. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |