| Plan Review Notes For Permit 16051093 |
| Permit Number |
16051093 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-31 13:04:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE ADDITION OF THE NEW SPRINKLER HEADS MAY | | | NEGATIVELY AFFECT THE EXISTING HYDRAULIC CALCUALTIONS | | | AND SYSTEM PERFORMANCE. | | | | | | PLEASE PROVIDE NEW HYDRAULIC CALCULATIONS INDICATING | | | PROPER SYSTEM PERFORMANCE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|