| 2017-03-23 11:13:16 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16071078 |
| | ADD: 1718 PARKER AVENUE/ FIRE STATION # 4 |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-662-8049 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | DATE: THURS. MARCH 23/ 2017 |
| | ACTION: DENIED |
| | |
| | |
| | 1) MISSING DOCUMENTS 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION: |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | |
| | 1A) 3RD REQUEST/ SEMI-COMPLIED, ONLY 2 ORIGINAL SIGNED |
| | & SEALED SOILS REPORTS WERE PROVIDED. SOILS REPORTS |
| | SUBMITTED ARE COPIES THEY DO NOT HAVE THE ENGINEERS |
| | ORIGINAL SIGNATURE. SOILS REPORT: 2014 FBC-B 1803.5.2 |
| | QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| | OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 2) 4/04/2017 BUILDING PROVISO: E-MAILED THE ARCHITECT |
| | AND BUILDER THERE IS NO LONGER A NEED FOR A RESIDENT |
| | INSPECTOR, I SPOKE WITH TTHE BUILDIJNG OFFICIAL ROBERT |
| | BROWN AND WILL REQUIRE THE CONTRACTOR TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING |
| | |
| | 3) SHEET LS-200: 4A) BUILDING PROVISO: WILL BE PROVIDED |
| | BY THE CONTRACTOR PRIOR TO CONSTRUCTION AS A SHOP |
| | DRAWING. DEFERRED SUBMITTAL. PLEASE PROVIDE THE AREA |
| | CONCRETE BLOCK MANUFACTURER THAT WILL BE PROVIDING THE |
| | 2 HOUR FIRE RATED BLOCK, IN THE EQUIVALENT THICKNESS |
| | PER 2014 FBC-B TABLE 722.3.2. |
| | |
| | 4) BUILDING PROVISO: SHEET A-102A INDICATES A FIRE |
| | RATED CHASE FOR THE RANGE EXHAUST DUCT, THE DETAIL IS |
| | FOR SHALT WALL CONSTRUCTION, PLEASE PROVIDE A DETAIL |
| | HOW THE BOTTOM OF THE SHAFT WILL BE SEALED OR |
| | PENETRATION THROUGH THE RATED FLOOR. 713.11 ENCLOSURE |
| | AT THE BOTTOM. SHOP DRAWINGS ARE TO BE SUBMITTED TO THE |
| | BUILDING DEPARTMENT INDICATING THE EXACT PRODUCT THAT |
| | ARE TO BE INSTALLED. |
| | |
| | 5) BUILDING PROVISO: DEFERRED SUBMITTALS. MISSING |
| | PRODUCT APPROVALS: 2014 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS - FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH |
| | OPENING SIZE. |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |