| Date |
Text |
| 2016-09-14 17:23:30 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16051078 |
| | 9/14/16 |
| | |
| | 1) 1ST REVIEW COMMENTS #1, 2, 5 & 6 STIL EXIST. PER THE |
| | ARCHITECT'S NARRATIVE THE REQUESTED EXHAUST VENTILATION |
| | AND AIR BALANCE CALCULATIONS, AND CORRECTED O/A CFMS |
| | FOR SOME OF THE ROOMS ARE SHOWN ON SHEET M6.1, HOWEVER |
| | M6.1 DOES NOT APPEAR TO HAVE BEEN REVISED. PLEASE |
| | PROVIDE THE REVISED SHEET. |
| | |
| | 2) REFER TO SECTION 404.1, ITEMS 1 AND 2 AND INDICATE |
| | HOW THE EXHAUST SYSTEM IN THE APPARATUS BAY WILL |
| | FUNCTION. VERIFY COMPLIANCE WITH SECTION 404.2 FOR |
| | MINIMUM VENTILATION RATE, AND THE REQUIRED 0.75 CFM PER |
| | SQ.FT. RATE CAPABILITY. |
| | |
| | 3) IN RESPONSE TO 1ST REVIEW COMMENT #3, THE ARCHITECT |
| | STATES THAT 100% OF THE RETURN AIR TO OARTU-1 IS BEING |
| | EXHAUSTED. HOW IS THIS POSSIBLE IF THE OARTU IS |
| | PRODUCING 2160 CFMS OF SUPPLY AIR, AND THE ERV HAS |
| | INTAKE AND EXHAUST CAPACITIES OF 850 CFMS? AS |
| | PREVIOUSLY REQUESTED PROVIDE THE LEAKAGE RATE OF THE |
| | ERV AS INDICATED BY THE MANUFACTURER'S SPECIFICATIONS. |
| | PLEASE |
| | |
| | SEETABLE 403.3 FOOTNOTE G AS IT APPLIES TO THE |
| | RECIRCULATION OF TOILET ROOM EXHAUST. |
| | |
| | 4) AS PREVIOUSLY REQUESTED PROVIDE THE FLEX DUCT SIZES |
| | ON THE 1ST SND 2ND MECHANICAL FLOOR PLANS OR RELOCATE |
| | THE FLEX TABLE FROM M6.1 TO M2.1 & M2.2. |
| | |
| | 5) AS PREVIOUSLY REQUESTED PROVIDE REVISED ENERGY |
| | CALCULATIONS THAT INCLUDE CU-1 & CU-2. A) THE |
| | PREVIOSULY SUBMITTED CALCULATIONS INCLUDE AHU-5 WHICH |
| | IS NOT SHOWN ON THE PLANS. |
| | |
| | 6) REFER TO THE SUBMITTED AC CALCULATIONS FOR OARTU-1 |
| | AND CU-1 & CU-2, AND THE OARTU SCHEDULE. IT APPEARS THE |
| | OARTU-1 DOES NOT HAVE THE CAPACITY TO PROVIDE THE |
| | REQUIRED HEATING BTU'S. |
| | |
| | 7) AS PREVIOUSLY REQUESTED PROVIDE A DUCT SMOKE |
| | DETECTOR IN THE RETURN AIR SYSTEM OF OARTU-1. |
| | |
| | 8) M2.1, M2.3 & A-104: PLEASE SHOW THE DRYER EXHAUST |
| | TERMINATION ON THE MECHANICAL AND ARCHITECTURAL ROOF |
| | PLANS. SHOW THE LOCATION OF THE DRYER IN THE FLOOR |
| | PLANS. |
| | |
| | 9) INDICATE HOW ACCESS IS BEING PROVIDED FOR SERVICE OF |
| | THE ROOFTOP MECHANICAL EQUIPMENT- SEE SECTION 306.5. |
| | |
| | 10) IT APPEARS THAT EF-2 & EF-3 MAY BE LOCATED WITHIN |
| | 10' OF THE ROOF EDGES. VERIFY THE PARAPETS AT THESE |
| | LOCSTIONS ARE MINIMUM 42" HIGH FROM THE ROOF SURFACE OR |
| | PROVIDE GUARDS- SEE SECTION 304.11. |
| | |
| | 11) THE ARCHITECT IS REQUESTING DEFERRED SUBMITTALS FOR |
| | EXTERIOR MECHANICAL INSTALLATION ENGINEERING AND WIND |
| | LOAD COMPLIANCE. PLEASE REVIEW THE FOLLOWING WPB |
| | AMENDMENTS: |
| | |
| | A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |