| 2016-06-13 13:30:02 | 1) SUBMIT SPECIFICATIONS FOR THE GENERATOR, FUEL |
| | TANK,AND PIPING DETAILS. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 2) SEPARATE PERMITS WILL BE REQUIRED FOR THE BACKFLOW |
| | PREVENTERS. |
| | 3) SUBMIT SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. |
| | 4) SUBMIT A STORM WATER RISER DIAGRAM. SHOW THE SQUARE |
| | FOOTAGE DRAINED BY EACH DRAIN. THE SIZING SHALL INCLUDE |
| | ONE-HALF THE AREA OF ANY VERTICAL WALL THAT DIVERTS |
| | RAINWATER TO THE ROOF. COMPLY WITH 2014 FPC TABLE |
| | 1106.3 & 1106.2 (2), SEC.1106.4. |
| | 5) SHT. C4.01 - SHOW THE SIZE OF THE STORM DRAIN AND |
| | SANITARY LINES ON THE PLAN.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 6) SHT. C6.07 - THERE IS A DETAIL FOR AN OIL AND |
| | SEPARATOR ON THIS SHEET AND A DETAIL ON SHT. P0.1. THE |
| | DETAIL ON SHT. P0.1 COMPLIES WITH THE PLUMBING CODE. |
| | DELETE THE DETAIL ON C6.07. |
| | 7) SHT. C6.05 - A SAMPLING PORT IS REQUIRED ON THE |
| | DISCHARGE LINE FROM THE GREASE INTERCEPTOR AND THE OIL |
| | SEPARATOR. |
| | 8) SHT. L3.01 - THE BACKFLOW PREVENTER FOR THE |
| | IRRIGATION SYSTEM SHALL BE LOCATED AS CLOSE AS POSSIBLE |
| | TO THE METER PER THE CITY'S CROSS CONNECTION MANUAL. |
| | YOU MAY CONTACT UTILITITES AT 822-2240 FOR FURTHER |
| | DIRECTION. |
| | 9) THE LANDSCAPE/IRRIGATION PLANS ARE STAMPED "NOT FOR |
| | CONSTRUCTION". CLARIFY. |
| | 10) SHT. A1.04 - SHOW THE DISTANCE OF THE WATER HEATER |
| | EXHAUST FROM THE RANGE HOOD SUPPLY FAN AND ALSO FROM |
| | THE WATER HEATER INTAKE. SUBMIT DOCUMENTATION FROM THE |
| | MANUFACTURER SHOWING THESE MINIMUM REQS.ALSO, SEE SEC. |
| | 503.2.3 & 503.8 OF 2014 FGC. |
| | 11) SHT. A-400 - DETAIL #1 - THE CENTER TO CENTER |
| | MEASUREMENT BETWEEN THE URINAL AND THE LAVATORY SHALL |
| | BE A MINIMUM OF 30 INCHES. 2014 FPC SEC.405.3.1. |
| | 12) SHT. A-400 - DETAIL #1C & SHT.A-401 DETAIL 2D - THE |
| | TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES FROM |
| | THE THE FRONT OF THE TOILET BOWL TO THE CENTER OF THE |
| | DISPENSER. 2014 FAC SEC. 604.7. |
| | 13) SHT. A-400 - THE HANDICAPPED ACCESSIBLE TOILET SEAT |
| | HEIGHT SHALL BE 17-19 INCHES ABOVE THE FINISH FLOOR |
| | MEASURED TO THE TOP OF THE SEAT. SEE ELEVATION 1C. |
| | 14) IF THE ADA BATHING ROOM ON THE SECOND FLOOR IS TO |
| | BE UNISEX, IT SHALL NOT CONTAIN A URINAL. FAC |
| | SEC.213.2.1. |
| | 15) THIS BUILDING CONSISTS OF FOUR DIFFERENT OCCUPANCY |
| | TYPES: ASSEMBLY,BUSINESS, R-2 ( DORMITORY) AND S-2. |
| | PLACE ALL FOUR OCCUPANCIES ON THE PLANS AND THE |
| | OCCUPANT LOAD FOR EACH AREA. |
| | 16) SUBMIT INFORMATION AS TO WHAT TYPE OF ITEMS WILL BE |
| | STORED IN THE SUPPLY STORAGE ROOM.SHT. A-100 INDICATES |
| | A REINSTALLED COMPRESSOR.SUBMIT A COMPRESSED AIR RISER |
| | FOR REVIEW IF ANY HARD PIPING WILL BE INSTALLED. |
| | 17) THE WASHER & DRYER IN LAUNDRY ROOM # 51 SHALL |
| | COMPLY WITH THE 2014 FBC-ACCESSIBILITY SEC. 611. |
| | 18)THE ICE MACHINE SHALL BE PROVIDED WITH A BACKFLOW |
| | PREVENTER PERR 2014 FPC SEC.608.3. |
| | 19) THE BATHROOMS IN THE CAPTAIN'S AND LIEUTENANT'S |
| | DORM ROOM SHALL COMPLY WITH 2014 FAC SEC.213.2. |
| | 20) SHT. A-401 - ADA RESTROOM #38 - THE LOCATION AND |
| | HEIGHT OF THE SHOWER CONTROLS SHALL COMPLY WITH 2014 |
| | FAC SEC.608.5.1. |
| | 21) SHT. A-700 - THE WALLS AND PARTITIONS WITHIN 2 FEET |
| | OF OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL |
| | CCOMPLY WITH FBC SEC.1210.2.2. |
| | 22) SHT. P0.1 - INDICATE THE SIZE/CAPACITY OF THE |
| | EXPANSION TANK ON THE WATER HEATER DETAIL. |
| | 23) SHT. P0.1 - THE SHOWER IN THE DECON ROOM IS LABELED |
| | AS A HANDICAPPED SHOWER. CLARIFY. |
| | 24) SUBMIT AN EXPANDED WATER RISER DIAGRAM.THE PIPE |
| | SIZES ARE ILLEGIBLE.CLEARLY SIZE THE WATER LINES. |
| | 25) P5.1 - SIZE THE FLOOR DRAIN, SHOWER AND FLOOR SINK |
| | IN THE DECON ROOM. |
| | 26) SHT. P5.1 - FIRST FLOOR ADA RESTROOM (#3) & STAFF |
| | RESTROOM (#11) SHOWS A URINAL ON A WET VENT. ONLY |
| | FIXTURES WITHIN A BATHROOM GROUP ARE PERMITTED ON A WET |
| | VENT. REFER TO THE DEFINITION OF "BATHROOM GROUP" IN |
| | CHAPTER 2, DEFINITIONS OF THE PLUMBING CODE. |
| | 27) THE WASHING MACHINE IS NOT SHOWN ON THE SANITARY |
| | RISER DIAGRAM.THE WASTE STACK SHAL BE A MINIMUM OF 3 |
| | INCHES PER 2014 FPC SEC.406.2. |
| | 28) BATHROOM # 47 - 2ND FLOOR - THE URINAL IS NOT |
| | PERMITTED ON A WET VENT. ONLY FIXTURES WITHIN A |
| | BATHROOM GROUP ARE PERMITTED ON A WET VENT. REFER TO |
| | THE DEFINITION OF "BATHROOM GROUP" IN CHAPTER 2, |
| | DEFINITIONS OF THE PLUMBING CODE. |
| | 29) THE OIL SEPARATOR IS LABELED AS A GREASE TRAP ON |
| | THE SANITARY RISER DIAGRAM. PLEASE CORRECT. |
| | 30) 2ND FLOOR ADA RESTROOM (38) - THE SHOWER SHALL BE |
| | INDIVIDUALLY VENTED. |
| | 31) 2ND FLOOR ADA RESTROOM (38) - THE LAVATORY IS NOT |
| | VENTED. |
| | 32) A LAUNDRY INTERCEPTOR IS REQUIRED PER 2014 FPC |
| | SEC.1003.6. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |