| 2016-07-02 10:08:17 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1. UPDATE ALL CODE REFERENCES SHOWN ON SHEET E.01 TO |
| | SHOW FLORIDA BUILDING CODE 2014 5TH EDITION AND AS |
| | STATED ABOVE. |
| | 2. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL |
| | SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL |
| | SUFFICE. |
| | 3. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| | FOR GENERATOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT |
| | NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE |
| | AND DATA, SIGNAGE, WIRELESS SYSTEMS, TRUCK CHARGING |
| | STATIONS, ETC. A NOTE WILL SUFFICE. |
| | 4. PLEASE LABEL RECEPTACLE IN TO BE GFCI PROTECTED PER |
| | NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO BE GFCI. |
| | 5. PLEASE LABEL RECEPTACLE IN KITCHEN ALL TO BE GFCI |
| | PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK, ALL |
| | TO BE GFCI. |
| | 6. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL |
| | AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. FBC |
| | 107.3.5 |
| | 7. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5 |
| | 8. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC |
| | 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE |
| | DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS |
| | AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS |
| | REQUIRED. |
| | 9. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS |
| | FOR FEEDERS AND BRANCH CIRCUITS. |
| | 10. SHEET E5.1- GROUNDING ELECTRODE CONDUCTOR |
| | UNDERSIZED AT 2/0. SHOW 3/0 PER TABLE NEC 250.66. ALSO |
| | CORRECT NOTE 6 TO SHOW 3/0. |
| | 11. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO THE |
| | ELECTRICAL SCOPE OF WORK. |
| | 12. PROVIDE GENERAL NOTES TO SHEET E2.1 TO MAINTAIN |
| | REQUIRED DEPTH PER NEC 300.5 FOR ALL U/G CONDUIT. |
| | 13. PLEASE CLARIFY THE NON-REQUIRED COPS NOTES PROVIDED |
| | AS TO AHJ AUTHORIZATION TO EXCLUDE THE REQUIREMENTS OF |
| | NEC 708 TO THIS PROJECT. |
| | 14. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |