| Plan Review Notes For Permit 16051054 |
| Permit Number |
16051054 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-27 05:32:26 | 1) THE MINIMUM SIZE PIPE TO THE TANKLESS WATER HEATER | | | SHALL BE 1 INCH PER 2014 FGC TABLE 402.4 (2). | | | 2) THE PE TABLE NOTED ON THE PLANS IS LISTED FOR CSST | | | IN THE 2014 FUEL GAS CODE. THE PLAN REFERENCES THE 2010 | | | FBC. THE 2010 CODE HAS NOT BEEN IN EFFECT FOR ALMOST A | | | YEAR. SIZE THE SYSTEM ACCORDING TO THE TABLES IN THE | | | 2014 CODE. | | | 3) SPECIFY THE SIZING TABLE ON THE PLANS THAT IS BEING | | | USED FOR THE SCH. 40 METALLIC PIPE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|