2016-06-06 10:37:461ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1.GAS SIZING TABLE LISTED ON THE PLAN FOR THE PE PIPES
 NOT CORRECT IT'S FOR CSST AT 5PSI PLEASE CORRECT ON
 PLAN.
 PER WPB AMEND. TP FBC 107.2.1
  
 2.THE PE PIPE SHALL BE SIZED FOR 100FT LONGEST LENGTH
 IT SHOULD BE 11/2IN PER FBC FUEL GAS TABLE 402.4(21)
  
 3. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOK TOP
 AND WATER HEATER USING STANDARD METHOD PER FBC FUEL GAS
 SEC. 304.5.1
  
  