| Notes |
| Date |
Text |
| 2016-06-06 10:37:46 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1.GAS SIZING TABLE LISTED ON THE PLAN FOR THE PE PIPES | | | NOT CORRECT IT'S FOR CSST AT 5PSI PLEASE CORRECT ON | | | PLAN. | | | PER WPB AMEND. TP FBC 107.2.1 | | | | | | 2.THE PE PIPE SHALL BE SIZED FOR 100FT LONGEST LENGTH | | | IT SHOULD BE 11/2IN PER FBC FUEL GAS TABLE 402.4(21) | | | | | | 3. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOK TOP | | | AND WATER HEATER USING STANDARD METHOD PER FBC FUEL GAS | | | SEC. 304.5.1 | | | | | | |
|