Plan Review Notes
Plan Review Notes For Permit 16051031
Permit Number 16051031
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-23 09:53:31REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S
  
 - FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS.
  
 - FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
  
 - NEC 680.21(C), 680.22 POOL PUMPS, POOL LIGHTS SHALL
 HAVE GFCI PROTECTION FOR THERE DEDICATED BRANCH
 CIRCUITS.