| Date |
Text |
| 2016-06-28 15:47:04 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. |
| | CONTRACTOR MAY SUBMIT REQUIRED INFORMATION AFTER PERMIT |
| | IS ISSUED AND BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME. |
| | |
| | 1- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- DESIGNER OF RECORD TO SPECIFY ALL LIVE LOADS |
| | INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY NOTES "B" |
| | AND "G" OF TABLE R301.5 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| | SPECIFYING NAILS OR SCREWS, THEN SPECIFY TYPE AND |
| | NUMBER. IF SPECIFYING ROOF TILE ADHESIVE, THEN PROVIDE |
| | PRODUCT APPROVAL. |
| | |
| | 4- ENERGY CALCULATIONS SUBMITTED: |
| | A) CLARIFY WHY SPACES IN PAGE 2 OF 4 SPECIFIES THAT |
| | THERE IS NO KITCHEN IN THIS SINGLE FAMILY RESIDENCE?. |
| | REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) CLARIFY WHERE ARE THE TWO INSULATED DOORS SPECIFIED |
| | ON PAGE 3 OF 4. REVISE AS REQUIRED TO MATCH PLANS. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | NOTE: LABEL FOR DOORS AND WINDOWS WILL BE REQUIRED |
| | SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE |
| | ENERGY CALCULATIONS WHEN THE ENERGY CALCULATIONS ARE |
| | NOT USING THE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| | RECORD. |
| | |
| | C) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON THE TRUSS |
| | CONNECTOR SCHEDULE. NOTE: NEED TO UPDATE THE FLORIDA |
| | PRODUCT APPROVAL NUMBERS LISTED ON THE TRUSS CONNECTOR |
| | SCHEDULE. FLORIDA PRODUCT APPROVAL NEEDS TO BE FOR THE |
| | 2014 CODE VERSION NOT 2010. |
| | |
| | 6- DESIGNER OR RECORD TO APPROVE ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: |
| | PLEASE PLACE REVIEW STAMP ON THE FRONT OF THE COVER |
| | PAGE OF THE PRODUCT APPROVAL NOT ON THE BACK. STAMP ON |
| | THE BACK OF THE PAGE DON'T ALLOW FOR PROPER SCANNING OF |
| | THE DOCUMENTS FOR FILING PURPOSES. SEC. 107.2.1.4 CITY |
| | AMENDMENTS. |
| | |
| | 7- TRUSS PACKAGE SUBMITTED: |
| | A) NEED ENGINEER'S ORIGINAL SIGNATURE (NOT COPY OR |
| | RUBBER STAMP) AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTES WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | B) THE TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED |
| | BY THE DESIGNER OF RECORD AS REQUIRED BY SEC. 107.3.4.2 |
| | CITY AMENDMENTS. |
| | |
| | C) THE COVER PAGE IS MISSING THE BUILDING PROFESSIONAL |
| | DESIGNER OF RECORD INFORMATION AS REQUIRED BY F.A.C. |
| | SEC. 61G15-31.003. |
| | |
| | D) ALL GENERAL DETAILS NEED TO BE SIGNED AND SEALED AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | E) INDIVIDUAL TRUSSES ARE DESIGNED BASED ON THE 2010 |
| | FBC. NEED TO REVISE USING THE CURRENT BUILDING CODE. |
| | REVISE THE GENERAL INFORMATION IN THE MIDDLE PAGE OF |
| | EACH INDIVIDUAL TRUSS AND NOTE #1 OF EACH INDIVIDUAL |
| | TRUSS. REVISE AS REQUIRED. CHAPTER 553 FLORIDA-STATUTE. |
| | |
| | F) INDIVIDUAL TRUSSES NEED TO BE DESIGNED FOR THE ATTIC |
| | LIVE LOAD AS REQUIRED BY NOTES "B" AND "G" OF TABLE |
| | R301.5 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS |
| | REQUIRED. |
| | |
| | G) THE INDIVIDUAL TRUSSES ARE NOT PROPERLY NUMBERED TO |
| | MATCH INDEX SHEET AS REQUIRED BY F.A.C. SEC. |
| | 61G15-31.003. |
| | |
| | H) THE LETTERING OF THE INDIVIDUAL TRUSSES IS TOO |
| | SMALL. IT'S NOT LEGIBLE. PROVIDE BIGGER AND LEGIBLE |
| | LETTERING. SEC. 107.2.1.4 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD |
| | SHEET. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |