| Plan Review Notes For Permit 16050998 |
| Permit Number |
16050998 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-01 11:49:38 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050998 | | | 6/1/2016 | | | | | | 1) SHEETS M202A, 203A, 204A, 205A, & 304A: PLEASE | | | CLARIFY HOW O/A IS BEING SUPPLIED TO THE RESIDENTIAL | | | UNITS, AND PROVIDE VENTILATION CALCULATIONS PER TABLE | | | 403.3. | | | 2) SHEET M201A: THE 1-WAY SUPPLY DIFFUSER IN THE POOL | | | ACCESS ROOM 135A HAS A LABEL INDICATING -200 RETURN | | | CFMS. | | | 3) REVISE THE EQUIPMENT SCHEDULES FOR THE KITCHEN | | | SUPPLY FANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|