2016-08-18 09:04:32ALTHOUGH THE STRUCTURE IS NOT A THRESHOLD BUILDING AND
 THE BUILDING DEPT. DOEW NOT REQUIRE A RESIDENT
 INSPECTOR, THE SPECIAL INSPECTOR NOTE ON PG S1.1
 INDICATES THE OWNER WISHES TO USE A RESIDENT INSPECTOR.
 EITHER REMOVE THIS REFERENCE TO SPECIAL INSPECTIONS BY
 A RESIDENT INSPECTOR OR SUBMIT THREE COPIES OF THE
 RESIDENT INSPECTER AGREEMENT TO THE CITY FOR REVIEW.