| Plan Review Notes For Permit 16050968 |
| Permit Number |
16050968 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-08-17 15:16:06 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1) 2ND REQUEST, NOT ADDRESSED. PROVIDE A ONE-LINE | | | DIAGRRAM SHOWING FEEDER SIZES & MAIN OVERCURRENT | | | PROTECTION, INCLUDE A PANEL SCHEDULE REFLECTING CONDUIT | | | SIZES, BRANCH CIRCUIT SIZES AND CIRCUIT LABELING | | | MATCHING FLOOR PLAN, LASTLY A GROUNDING DETAIL AND LOAD | | | CALCULATIONS FOR THE GUARD BOOTH. FBC 107 | | | | | | 2) 2ND REQUEST, NOT ADDRESSED. PROVIDE A SITE PLAN | | | SHOWING FEEDER CONDUCTOR ROUTING AND A FLOOR PLAN | | | REFLECTING ALL ELECTICAL OUTLETS INVOLVED. FBC 107 | | | MINIMUM PLAN REVIEW |
|