| 2016-06-20 14:52:17 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | DATE: 6/20/16 |
| | ACTION: DENIED |
| | |
| | 1. PROVIDE PRODUCT APPROVALS FOR NEW SLIDING GLASS |
| | DOOR. |
| | 2. IF IN-FILL OF WALL WILL BE SITE BUILT, PROVIDE |
| | DETAILS FOR HEADER, POST'S, ALL WELDS AND WELDER |
| | CERIFICATIONS. |
| | 3. IF IN-FILL OF WALL WILL BE MANUFACTURED OFF-SITE, |
| | PROVIDE CERTIFICATION OF APPROVED INDEPENDANT TESTING |
| | LAB, CERTIFICATION OF WELDING SHOP AND WELDER |
| | CERTIFICATIONS. |
| | 4. GENERAL NOTES ON PG S1.1 REQUIRES INSPECTIONS BY " |
| | AN INDEPENDANT TESTING LAB APPROVED PRIOR TO STARTING |
| | CONSTRUCTION BY THE BUILDING DEPT." PROVIDE 3 COPIES OF |
| | RESIDENT INSPECTOR AGREEMENT TO BE REVIEWED AND |
| | APPROVED BY KEN CONRAD, CHIEF BUILDING INSPECTOR PRIOR |
| | TO THE ISSUANCE OF A PERMIT. |
| | 5. PROVIDE DETAIL OF NEW SLAB TO EXISTING SLAB |
| | CONNECTION. |
| | 6. ELECTRICAL PERMIT REQUIRED. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY |
| | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, |
| | WINDOW AND DOOR SUBMITTALS. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| | SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A |
| | CERTIFICATE CALLED FOR BY ANY PROVISION OF THE |
| | TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS |
| | UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A |
| | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | |
| | |
| | |
| | |
| | |