2016-09-28 14:54:55REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1] NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL
 BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.