| 2016-09-28 14:54:55 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO | | | | | | 1] NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL | | | BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR | | | MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY | | | BE ON OWN CIRCUIT. |
|