Plan Review Notes
Plan Review Notes For Permit 16050966
Permit Number 16050966
Review Stop B
Sequence Number 2
Notes
Date Text
2016-07-26 15:57:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. IF A STAIR IS PROPOSED, PROVIDE A DETAIL FOR THE
 STAIR AND LANDING, FBC 1009, 1009.8.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THIS IS NOT
 REQUIRED TO BE ACCESSIBLE. THE CODE SECTION REFERENCED
 IS FROM CHAPTER 10, FLORIDA BUILDING CODE, BUILDING.
 THIS IS A STAIR IN THE EXIT DISCHARGE AND IS TO COMPLY
 WITH THE REQUIREMENTS OF FBC 1009.
  
 REVISE PLAN TO SHOW A LANDING WHICH COMPLIES WITH
 1009.8 OR REVISE TO INCLUDE EXCEPTION.
  
 IF THE STAIR IS NOT INTENDED TO MEET THE REQUIREMENTS
 OF FBC 5TH EDITION ACCESSIBILITY, REVISE PLAN TO
 INCLUDE APPLICABLE EXCEPTIONS INCLUDING CODE SECTION.
  
 THE STAIR SHOWN DOES NOT HAVE HANDRAILS, FBC BUILDING
 1009.15. PROVIDE A DETAIL.
  
 FBC 553, A 4X PLAN REVIEW FEE IS REQUIRED TO BE
 ASSESSED IF COMMENT IS NOT ADDRESSED A THIRD TIME (LIFE
 SAFETY)
  