| Notes |
| Date |
Text |
| 2016-07-26 15:57:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS LIST: | | | | | | 1. IF A STAIR IS PROPOSED, PROVIDE A DETAIL FOR THE | | | STAIR AND LANDING, FBC 1009, 1009.8. | | | | | | 2ND REVIEW, RESPONSE LETTER STATES THAT THIS IS NOT | | | REQUIRED TO BE ACCESSIBLE. THE CODE SECTION REFERENCED | | | IS FROM CHAPTER 10, FLORIDA BUILDING CODE, BUILDING. | | | THIS IS A STAIR IN THE EXIT DISCHARGE AND IS TO COMPLY | | | WITH THE REQUIREMENTS OF FBC 1009. | | | | | | REVISE PLAN TO SHOW A LANDING WHICH COMPLIES WITH | | | 1009.8 OR REVISE TO INCLUDE EXCEPTION. | | | | | | IF THE STAIR IS NOT INTENDED TO MEET THE REQUIREMENTS | | | OF FBC 5TH EDITION ACCESSIBILITY, REVISE PLAN TO | | | INCLUDE APPLICABLE EXCEPTIONS INCLUDING CODE SECTION. | | | | | | THE STAIR SHOWN DOES NOT HAVE HANDRAILS, FBC BUILDING | | | 1009.15. PROVIDE A DETAIL. | | | | | | FBC 553, A 4X PLAN REVIEW FEE IS REQUIRED TO BE | | | ASSESSED IF COMMENT IS NOT ADDRESSED A THIRD TIME (LIFE | | | SAFETY) | | | |
|