2016-06-02 09:04:55REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
  
 - 1006.2 THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL
 NOT BE LESS THAN 1 FOOTCANDLE (11 LUX) AT THE WALKING
 SURFACE. THE MEANS OF EGRESS, INCLUDING THE EXIT
 DISCHARGE, SHALL BE ILLUMINATED AT ALL TIMES THE
 BUILDING SPACE SERVED BY THE MEANS OF EGRESS IS
 OCCUPIED.
  
  
  