| Plan Review Notes For Permit 16050966 |
| Permit Number |
16050966 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-02 09:04:55 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL BE | | | FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR | | | MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY | | | BE ON OWN CIRCUIT. | | | | | | - 1006.2 THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL | | | NOT BE LESS THAN 1 FOOTCANDLE (11 LUX) AT THE WALKING | | | SURFACE. THE MEANS OF EGRESS, INCLUDING THE EXIT | | | DISCHARGE, SHALL BE ILLUMINATED AT ALL TIMES THE | | | BUILDING SPACE SERVED BY THE MEANS OF EGRESS IS | | | OCCUPIED. | | | | | | | | | |
|