Plan Review Notes
Plan Review Notes For Permit 16050959
Permit Number 16050959
Review Stop M
Sequence Number 2
Notes
Date Text
2017-02-24 07:41:332ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16050959
 2/24/17
  
 1) SHEET A1.04G: THE NATURAL VENTILATION CALCULATION
 FOR THE GARAGES SHOWN ON THE PLAN IS NOT IN COMPLIANCE
 WITH SECTION 402.2. PLEASE PROVIDE A CALCULATION THAT
 INDICATES THE MINIMUM OPENABLE AREA TO THE OUTDOORS
 SHALL BE AT LEAST 4% OF THE FLOOR AREA.
 PLEASE NOTE THAT THE WPB FIRE DEPT. HAS NOT APPROVED
 NATURAL VENTILATION FOR THE GARAGES- SEE FIRE COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  