| Plan Review Notes For Permit 16050959 |
| Permit Number |
16050959 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-02-24 07:41:33 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16050959 | | | 2/24/17 | | | | | | 1) SHEET A1.04G: THE NATURAL VENTILATION CALCULATION | | | FOR THE GARAGES SHOWN ON THE PLAN IS NOT IN COMPLIANCE | | | WITH SECTION 402.2. PLEASE PROVIDE A CALCULATION THAT | | | INDICATES THE MINIMUM OPENABLE AREA TO THE OUTDOORS | | | SHALL BE AT LEAST 4% OF THE FLOOR AREA. | | | PLEASE NOTE THAT THE WPB FIRE DEPT. HAS NOT APPROVED | | | NATURAL VENTILATION FOR THE GARAGES- SEE FIRE COMMENTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|