| Plan Review Notes For Permit 16050959 |
| Permit Number |
16050959 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-02-23 13:35:35 | PERMIT # 16050959 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | | | | 1) NATURAL VENTILATION HAS NOT BEEN APPROVED FOR THE | | | GARAGE UNITS. THE MECHANICAL VENTILATION REQUIREMENTS | | | UNDER NFPA 88 HAVE NOT BEEN MET. | | | PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING | | | STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM | | | CAPABLE OF PROVIDING A MINIMUM OF 1FT3/MIN PER FT2 OF | | | FLOOR AREA. MECHANICAL VENTILATING SYSTEMS SHALL BE | | | INSTALLED IN ACCORDANCE WITH NFPA 90A. DUCTWORK SHALL | | | BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIAL. | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 |
|