 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) NATURAL VENTILATION HAS NOT BEEN APPROVED FOR THE
 GARAGE UNITS. THE MECHANICAL VENTILATION REQUIREMENTS
 UNDER NFPA 88 HAVE NOT BEEN MET.
 PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1FT3/MIN PER FT2 OF
 FLOOR AREA. MECHANICAL VENTILATING SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 90A. DUCTWORK SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIAL.
  