Plan Review Notes
Plan Review Notes For Permit 16050949
Permit Number 16050949
Review Stop M
Sequence Number 1
Notes
Date Text
2016-05-25 17:52:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050949
 5/25/16
  
 1) INDICATE THE MAKE AND MODEL AND COOLING AND HEATING
 CAPACITIES OF THE EXISTING AC SYSTEM.
 2) THE 8X12" TRUNK AND 10" ROUND DUCT ARE UNDERSIZED
 FOR 750 CFM'S OF SUPPLY AIR PER BY STANDARD ACCA DUCT
 SIZING CALCULATORS. PROVIDE A MINIMUM 8X16" TRUNK AND
 12" ROUND DUCT AND SHOW THEIR POINT OF CONNECTION.
 3) THE 6" RETURN AIR TRANSFER DUCT FROM BEDROOM-3 TO
 THE LIVING ROOM SHALL BE MINIMUM 8"- SECTION 601.5
 FBC-14 MECHANICAL.
 4) PROVIDE AN EXHAUST VENTILATION PLAN FOR THE NEW
 COOKTOP IN COMPLIANCE WITH SECTION 505.1. SHOW THE HOOD
 AND EXHAUST DUCT SIZES, EXHAUST DUCT RUN, AND
 TERNINATION LOCATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE COOKTOP AND THE EXHAUST SYSTEM.
 PLEASE NOTE THAT MAKEUP AIR WILL BE REQUIRED IF THE
 SYST3EM IS CAPABLE OF EXHAUSTING IN EXCESS OF 400
 CFM'S.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  