| Plan Review Notes For Permit 16050921 |
| Permit Number |
16050921 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-20 17:24:41 | | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE WILKINS MODEL 720 A DOES NOT MEET THE .25% PB TO | | | MEET THE LEAD FREE NSF 61 STANDARDS IT IS ON THE USC | | | LIST BUT IF YOU LOOK AT THE .25% PB IT INDICATES A NO. | | | | | | TYPE: PVB MANUFACTURER: WILKINS MODEL: 720A | | | SIZE: 1 ORIENTATION: VUH METERS: | | | MANUAL: 5 ( 0.25% PB: NO) SPARE PARTS ONLY: NO | | | APPROVED: 28-AUG-1978 RENEWED: 28-AUG-2014 BYPASS: | | | SHUTOFFS: (II),OOO | | | NOTES: BEGINNING WITH SERIAL NO. T00001 THE TEST COCKS | | | WERE MOVED FROM THE BODY TO THE SHUTOFF VALVES. | | | 2015 ? UNIVERSITY OF SOUTHERN CALIFORNIA | | | | | | THE WILKINS MODEL 420 XL IS THE ONLY WILKINS MODEL THAT | | | MEETS THE LEAD FREE REQUIREMENT. | | | | | | TYPE: PVB MANUFACTURER: WILKINS MODEL: 420XL | | | SIZE: 1 ORIENTATION: VUH METERS: | | | MANUAL: 9 ( 0.25% PB: YES) SPARE PARTS ONLY: YES | | | APPROVED: 03-AUG-2011 RENEWED: 03-AUG-2014 BYPASS: | | | SHUTOFFS: (IIII) | | | | | | | | | 2.PLEASE INDICATE ON THE PERMIT APPLICATION AND | | | MANUFACTURE SPEC WHAT SIZE YOUR USING. | | | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | | | | |
|