Plan Review Notes
Plan Review Notes For Permit 16050921
Permit Number 16050921
Review Stop P
Sequence Number 1
Notes
Date Text
2016-05-20 17:24:41 
  
 PLUMBING COMMENTS:
  
 1. THE WILKINS MODEL 720 A DOES NOT MEET THE .25% PB TO
 MEET THE LEAD FREE NSF 61 STANDARDS IT IS ON THE USC
 LIST BUT IF YOU LOOK AT THE .25% PB IT INDICATES A NO.
  
 TYPE: PVB MANUFACTURER: WILKINS MODEL: 720A
 SIZE: 1 ORIENTATION: VUH METERS:
 MANUAL: 5 ( 0.25% PB: NO) SPARE PARTS ONLY: NO
 APPROVED: 28-AUG-1978 RENEWED: 28-AUG-2014 BYPASS:
 SHUTOFFS: (II),OOO
 NOTES: BEGINNING WITH SERIAL NO. T00001 THE TEST COCKS
 WERE MOVED FROM THE BODY TO THE SHUTOFF VALVES.
 2015 ? UNIVERSITY OF SOUTHERN CALIFORNIA
  
 THE WILKINS MODEL 420 XL IS THE ONLY WILKINS MODEL THAT
 MEETS THE LEAD FREE REQUIREMENT.
  
 TYPE: PVB MANUFACTURER: WILKINS MODEL: 420XL
 SIZE: 1 ORIENTATION: VUH METERS:
 MANUAL: 9 ( 0.25% PB: YES) SPARE PARTS ONLY: YES
 APPROVED: 03-AUG-2011 RENEWED: 03-AUG-2014 BYPASS:
 SHUTOFFS: (IIII)
  
  
 2.PLEASE INDICATE ON THE PERMIT APPLICATION AND
 MANUFACTURE SPEC WHAT SIZE YOUR USING.
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved