| 2017-01-10 17:47:30 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16050912 |
| | NORTON MUSUEM |
| | 1/10/17 |
| | |
| | 1) 3RD REQUEST FOR AC COOLING AND HEATING CALCULATIONS. |
| | |
| | 2) THE REVISED ENERGYGAUGE COMPLIANCE FORM WAS |
| | SUBMITTED WITHOUT THE OWNER/AGENT'S SIGNATURE. |
| | |
| | 3) 3RD REQUEST FOR COMPLETE VENTILATION CALCULATIONS. |
| | THE CALCULATIONS ON M607 ARE FOR THE ROOMS AND SPACES |
| | UTILIZING THE IAQ PROCEDURE - SYSTEMS 3, 18, 19,20,21,& |
| | 22, HOWEVER MINIMUM VENTILATION CALCULATIONS ARE |
| | REQUIRED FOR ALL OF THE OTHER ROOMS AND SPACES I.E. THE |
| | FIRST FLOOR GALLERIES AND DINING AREAS ON THE SOUTH |
| | END- SYSTEMS 14 & 15. PLEASE NOTE THAT DEMAND |
| | CONTROLLED VENTILATION MAY BE REQUIRED- SEE SECTION |
| | C403.2.5.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | 4) 3RD REQUEST FOR EXHAUST VENTILATION CALCULATIONS FOR |
| | THE CHILLER ROOM , AND AN EQUIPMENT SCHEDULE FOR EF-9. |
| | |
| | 5) 3RD REQUEST FOR DUCT SMOKE DETECTORS TO BE SHOWN IN |
| | THE RETURN AIR SYSTEMS OF THE AHU'S. |
| | |
| | 6) 3RD REQUEST TO SHOW THE MISSING SMOKE AND FIRE |
| | DAMPERS: |
| | REFER TO SECTION 607.5.4.AND PROVIDE SMOKE DAMPERS FOR |
| | ALL DUCTS LISTED BELOW THAT PENETRATE SMOKE BARRIERS, |
| | UNLESS MEETING ONE OF THE THREE EXCEPTIONS LISTED UNDER |
| | THE SECTION. |
| | M121.5- 12X10 DUCT AT SMITH GALLERY 131/RESTROOM WALL. |
| | M121.8- 38X14 & 42X14 DUCTS AT LAUDER RESTAURANT |
| | 120/LOBBY 118/CORRIDOR 113 WALLS. |
| | M122.8- 12X12 AT CONFERENCE 223/MCGRAW 225. |
| | 30X12 AT MCGRAW 225/VESTIBULE 226. |
| | 14X10 AT MARDEN 226/MCGRAW 225. |
| | M123.7- ALL DUCTS TRAVERSING THROUGH THE MARDEN GALLERY |
| | 226/ CLASSROOM 221/ THE ADMISSIONS/GRAND HALL/& OFFICES |
| | 209 & 210. |
| | M123.8- DUCTS AT CORRIDOR 301/MEP & GROSS GALLERY 304. |
| | M123.8:FSD'S FOR DUCTS PENETRATING THE SHAFT AT |
| | CORRIDOR 301. |
| | PROVIDE KEY NOTES AT ALL FD, FSD, AND SD DAMPER |
| | LOCATIONS. |
| | . |
| | 7) INDICATE HOW ACCESS WILL BE PROVIDED TO THE FIRE |
| | DAMPERS LOCATED AT THE FLOOR/CEILING ASSEMBLY ABOVE THE |
| | STILLER AUDITORIUM. |
| | |